{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2110-0HA15-1AP6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2110-0HA15-1AP6","canonicalUrl":"https://aoctrl.com/siemens/3RA2110-0HA15-1AP6","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2110-0HA15-1AP6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2110-0HA15-1AP6 non-fused motor starter, direct starter, size S00, 180 W at 400 V, Class 10, 50/60 Hz, snap-on DIN rail.","salesMarkdown":"The Siemens 3RA2110-0HA15-1AP6 is a SIRIUS 3RA2 non-fused direct starter, size S00, combining a 3RT2015-1AP61 contactor and a 3RV2011-0HA10 circuit-breaker with a thermal bimetallic overload relay and magnetic short-circuit trip in one assembly. Rated 180 W at 400 V, 250 W at 500 V, and 370 W at 690 V in AC-3 duty, with a Class 10 trip characteristic — it protects standard three-phase squirrel-cage motors during start-up and running overloads. The unit snaps onto a DIN rail or screws into a panel using the additional push-in lug, with a vertical mounting position specified. Clearance requirements are 20 mm upwards, 10 mm downwards, and 9 mm at the side — no space needed forwards or backwards. ## Motor power ratings and trip coordination At 500 V the same starter handles 250 W, and at 690 V it reaches 370 W. The magnetic short-circuit trip handles fault clearing independently of the thermal element, so a hard short is interrupted without waiting for the bimetal to heat up. ## Supplied components and wiring This order code ships as a complete assembly: the 3RT2015-1AP61 contactor, the 3RV2011-0HA10 circuit-breaker, and the 3RA1921-1DA00 link module that interconnects them. The auxiliary switch extension is available (product extension auxiliary switch: Yes), so adding a signalling contact for the PLC is a field-fit option. AWG equivalents are 2× (20 to 16) for the contactor and 2× (18 to 14) plus 2× 12 for the circuit-breaker side. ## Environmental and compliance envelope Pollution degree 3 means it tolerates conductive pollution in industrial control panels — no additional conformal coating required for normal factory environments.","metaTitle":"Siemens 3RA2110-0HA15-1AP6 SIRIUS Motor Starter","metaDescription":"Siemens 3RA2110-0HA15-1AP6 SIRIUS non-fused motor starter, 180 W at 400 V, Class 10, size S00. Active production, quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Depth":"97.1 mm","Width":"45 mm","title":"3RA2110-0HA15-1AP6","Height":"167.2 mm","Upwards":"20 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"690 V","description":"Fuseless motor starter Direct start 600VAC Size S00 0.55-0.8A 220/240VAC 50/60HZ screw connection For screw mounting Or 35 mm rail-mounting Type of coordination 2 IQ = 150 KA Also full fills type Of coordination 1 1NO (contactor)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Snap-mounted to DIN rail or screw-mounted with additional push-in lug","Mounting Position":"vertical","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Degree Of Pollution":"3","Product Designation":"non-fused motor starter 3RA2","Size Of Load Feeder":"S00","at 400 V rated value":"180 W","at 50 Hz rated value":"187 ... 242 V","at 500 V rated value":"250 W","at 60 Hz rated value":"192 ... 264 V","at 690 V rated value":"370 W","Design Of The Product":"direct starter","Of The Supplied Contactor":"3RT2015-1AP61","For Main Contacts Stranded":"0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)","Of The Supplied Link Module":"3RA1921-1DA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","Design Of The Overload Release":"thermal (bimetallic)","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","at AWG cables for main contacts":"2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0HA10","Product Extension Auxiliary Switch":"Yes","Surge Voltage Resistance Rated Value":"6 kV","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"4.8 VA","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"6g / 11 ms","at 400 V according to IEC 60947-4-1 rated value":"153 000 A","at 500 V according to IEC 60947-4-1 rated value":"100 000 A","at 690 V according to IEC 60947-4-1 rated value":"100 000 A","operational current at AC-3 at 400 V rated value":"0.6 A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Mechanical Service Life (Switching Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"10.4 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d67b4ff3eebb828bbc27bf2f68c9ca2f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=334384&mlfb=3RA2110-0HA15-1AP6"},"ai":{"faq":[{"question":"What motor power does 3RA2110-0HA15-1AP6 handle at 400 V?","answer":"At 500 V it handles 250 W, and at 690 V it reaches 370 W."},{"question":"What components are supplied with the 3RA2110-0HA15-1AP6?","answer":"The assembly includes the 3RT2015-1AP61 contactor, the 3RV2011-0HA10 circuit-breaker, and the 3RA1921-1DA00 link module. The auxiliary switch is available as a field-fit extension."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2110-0HA15-1AP6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2110-0HA15-1AP6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}