{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2110-1GH15-1AP0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2110-1GH15-1AP0","canonicalUrl":"https://aoctrl.com/siemens/3RA2110-1GH15-1AP0","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2110-1GH15-1AP0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2110-1GH15-1AP0 direct-on-line motor starter, Size S00, CLASS 10, 45 mm width, 2.2 kW at 400 V, spring-loaded terminals, for 60 mm busbar systems.","salesMarkdown":"## SIRIUS direct-on-line starter, Size S00 The Siemens 3RA2110-1GH15-1AP0 is a SIRIUS direct-on-line motor starter in Size S00, designed for snapping onto 60 mm busbar systems. It ships with the 3RT2015-2AP01 contactor and the 3RA2911-2AA00 link module, so the assembly is a single order code — no separate picking of contactor and overload relay. ## Trip Class 10 and motor protection The 2.2 kW rating at 400 V (50/60 Hz) covers the common 3 hp motor frame at 460/480 V. Spring-loaded terminals on the main current circuit eliminate the need for screwdriver torque checks; the cage clamp holds the conductor under vibration. The 45 mm width fits standard 45 mm busbar pitch, and the 155 mm depth leaves room for cable bending inside the enclosure. ## Mounting and clearance on 60 mm busbars Snaps directly onto 60 mm busbar systems — no DIN rail adapter needed. Mounting position is vertical only. Clearance requirements: 50 mm upwards, 20 mm forwards, 20 mm at the side, 10 mm downwards, 0 mm backwards. The 260 mm height and 155 mm depth mean the starter will fit a standard 300 mm deep enclosure with room for the outgoing cable bend.","metaTitle":"Siemens 3RA2110-1GH15-1AP0 SIRIUS Motor Starter, Size S00","metaDescription":"Siemens 3RA2110-1GH15-1AP0 SIRIUS direct-on-line motor starter, Size S00, CLASS 10, 45 mm wide, 2.2 kW at 400 V. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"155 mm","Width":"45 mm","title":"3RA2110-1GH15-1AP0","Height":"260 mm","Upwards":"50 mm","Forwards":"20 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"20 mm","Rated Value":"690 V","description":"Load feeder fuseless, Direct-on-line starting 400 V AC, Size S00 4.50...6.30 A 230 V AC Spring-type terminal for 60 mm busbar systems Type of coordination 1, Iq = 150 kA 1 NO (contactor)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"for snapping onto 60 mm busbar systems","Mounting Position":"vertical","PROFIsafe protocol":"No","Product Brand Name":"SIRIUS","Type Of Assignment":"1","Product Designation":"Direct (on-line) starter","Size Of Load Feeder":"S00","PROFINET IO protocol":"No","at 230 V rated value":"0.75 hp","at 400 V rated value":"2 200 kW","at 480 V rated value":"4.8 A","at 50 Hz rated value":"230 ... 230 V","at 60 Hz rated value":"230 ... 230 V","at 600 V rated value":"6.1 A","Design Of The Product":"for 60 mm busbars","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-20 ... +60 °C","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1.5 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","Of The Supplied Contactor":"3RT2015-2AP01","Of The Supplied Link Module":"3RA2911-2AA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","at AC-3 at 400 V rated value":"6.3 A","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"6.3 A","Design Of The Overload Release":"thermal (bimetallic)","Of The Supplied Busbar Adapter":"8US1251-5DT11","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-1GA20","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Without Load Current Share Typical":"4.2 W","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.6 W","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"4.2 VA","protocol is supported AS-Interface protocol":"No","with high demand rate according to SN 31920":"73 %","reference code according to IEC 81346-2:2019":"Q","shock resistance according to IEC 60068-2-27":"6g / 11 ms","Type Of Voltage Of The Control Supply Voltage":"AC","at 400 V according to IEC 60947-4-1 rated value":"150 000 A","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Mechanical Service Life (Operating Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"82 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"4.5 ... 6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6feb8da1904d33f61e89df8e20c8c612.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=437340&mlfb=3RA2110-1GH15-1AP0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2110-1GH15-1AP0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2110-1GH15-1AP0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}