{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2115-0DA15-1AK6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2115-0DA15-1AK6","canonicalUrl":"https://aoctrl.com/siemens/3RA2115-0DA15-1AK6","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2115-0DA15-1AK6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2115-0DA15-1AK6 non-fused motor starter, size S00, Class 10 thermal bimetallic overload, 690 V AC-3, 45 mm width, 97.1 mm depth, 167.2 mm height, snap-on DIN rail.","salesMarkdown":"## Active production — what that means for your BOM line The 3RA2115-0DA15-1AK6: The unit ships as a direct starter assembly: the supplied 3RT2015-1AK61 contactor and 3RV2011-0DA15 circuit breaker are integrated via the 3RA1921-1DA00 link module, saving panel wiring time. ## Class 10 trip and the thermal overload decision The magnetic short-circuit trip handles the instantaneous fault clearance; the combination means one device covers both overload and short-circuit protection up to the SCCR of the downstream feeder. ## Panel fit — dimensions and mounting Mounting position is vertical only; the required clearance above the unit is 20 mm, below is 10 mm, and 9 mm at the sides — no extra space needed forward or backward. ## Rated voltage and power consumption across the line Surge voltage withstand is 6 kV, and the pollution degree is 3, so it's suitable for industrial environments with conductive dust or condensation — no additional conformal coating required for most panel builds. ## Wiring and auxiliary extension The product extension auxiliary switch is available (Yes), meaning you can add a side-mounted auxiliary contact block for status feedback to the PLC without modifying the main assembly.","metaTitle":"Siemens 3RA2115-0DA15-1AK6 SIRIUS Motor Starter, Class 10","metaDescription":"Siemens 3RA2115-0DA15-1AK6 SIRIUS non-fused motor starter, size S00, Class 10 thermal overload, 690 V AC-3. Active production, quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Depth":"97.1 mm","Width":"45 mm","title":"3RA2115-0DA15-1AK6","Height":"167.2 mm","Upwards":"20 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"690 V","description":"Fuseless motor starter Direct start 600VAC Size S00 0.22-0.32a 110/120VAC 50/60HZ screw connection For screw mounting Or 35 mm rail-mounting Type of coordination 2 IQ = 150 KA Also full fills type Of coordination 1 1NO+1NC (MSP) 1NO (contactor)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Snap-mounted to DIN rail or screw-mounted with additional push-in lug","Mounting Position":"vertical","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Degree Of Pollution":"3","Product Designation":"non-fused motor starter 3RA2","Size Of Load Feeder":"S00","at 400 V rated value":"90 W","at 50 Hz rated value":"93.5 ... 121 V","at 500 V rated value":"90 W","at 60 Hz rated value":"96 ... 132 V","at 690 V rated value":"120 W","Design Of The Product":"direct starter","Of The Supplied Contactor":"3RT2015-1AK61","For Main Contacts Stranded":"0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)","Of The Supplied Link Module":"3RA1921-1DA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","Design Of The Overload Release":"thermal (bimetallic)","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","at AWG cables for main contacts":"2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0DA15","Product Extension Auxiliary Switch":"Yes","Surge Voltage Resistance Rated Value":"6 kV","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"4.8 VA","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"2","shock resistance according to IEC 60068-2-27":"6g / 11 ms","at 400 V according to IEC 60947-4-1 rated value":"153 000 A","at 500 V according to IEC 60947-4-1 rated value":"100 000 A","at 690 V according to IEC 60947-4-1 rated value":"100 000 A","operational current at AC-3 at 400 V rated value":"0.3 A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Mechanical Service Life (Switching Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"4.16 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.22 ... 0.32 A","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0e7001a4401f9f9be90988b38cae1157.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=57823&mlfb=3RA2115-0DA15-1AK6"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RA2115-0DA15-1AK6?","answer":"No direct second-source cross-reference is available from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2115-0DA15-1AK6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2115-0DA15-1AK6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}