{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2120-4AD26-0FB4","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2120-4AD26-0FB4","canonicalUrl":"https://aoctrl.com/siemens/3RA2120-4AD26-0FB4","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2120-4AD26-0FB4","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2120-4AD26-0FB4 direct-on-line starter, size S0, 16 A at 400 V AC-3, Class 10 trip, 24 V DC coil, screw terminals, for snapping onto 60 mm busbar systems.","salesMarkdown":"## 16 A AC-3 at 400 V — the motor duty rating that governs the real load The 3RA2120-4AD26-0FB4: The same 16 A holds at 480 V and 600 V (cite:,), so the current rating does not derate across the common North American voltage range. Trip Class 10 (cite:) means the overload relay must trip within 10 seconds at seven times the current setting — the standard for most general-purpose motor starting where the thermal curve needs to protect the winding without nuisance tripping on a normal start. ## Busbar snap-on mounting — panel integration for 60 mm systems The starter is designed for snapping onto 60 mm busbar systems (cite:,) — the vertical mounting position (cite:) is mandatory to keep the contactor and overload relay within their published thermal envelope. Clearance requirements: 50 mm upward, 20 mm forward, 20 mm at the sides, 10 mm downward, and zero backward (cite:,). The supplied contactor is a 3RT2026-1FB40 (cite:) and the link module is a 3RA2921-1BA00 (cite:) — these are the factory-matched pair for this size S0 feeder. Main circuit connections are screw-type terminals (cite:).","metaTitle":"Siemens 3RA2120-4AD26-0FB4 SIRIUS direct starter, 16 A AC-3","metaDescription":"Siemens 3RA2120-4AD26-0FB4 SIRIUS direct-on-line starter, 16 A at 400 V AC-3, Class 10, size S0, for 60 mm busbar mounting. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"165 mm","Width":"45 mm","Height":"260 mm","Upwards":"50 mm","Forwards":"20 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"20 mm","Rated Value":"24 ... 24 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"for snapping onto 60 mm busbar systems","Mounting Position":"vertical","PROFIsafe protocol":"No","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Product Designation":"Direct (on-line) starter","Size Of Load Feeder":"S0","PROFINET IO protocol":"No","at 230 V rated value":"2 hp","at 400 V rated value":"7 500 kW","at 480 V rated value":"16 A","at 600 V rated value":"16 A","Design Of The Product":"for 60 mm busbars","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 110/120 V rated value":"1 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"5 hp","at 460/480 V rated value":"10 hp","Of The Supplied Contactor":"3RT2026-1FB40","Of The Supplied Link Module":"3RA2921-1BA00","Size Of The Circuit-Breaker":"S0","at AC-3 rated value maximum":"690 V","at AC-3 at 400 V rated value":"16 A","at AC-3e rated value maximum":"690 V","at AC-3e at 400 V rated value":"16 A","Design Of The Overload Release":"thermal (bimetallic)","Of The Supplied Busbar Adapter":"8US1251-5NT10","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2021-4AA10","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Without Load Current Share Typical":"5.9 W","holding power of magnet coil at DC":"5.9 W","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"5 W","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","protocol is supported AS-Interface protocol":"No","with high demand rate according to SN 31920":"73 %","reference code according to IEC 81346-2:2019":"Q","shock resistance according to IEC 60068-2-27":"6g / 11 ms","Type Of Voltage Of The Control Supply Voltage":"DC","at 400 V according to IEC 60947-4-1 rated value":"150 000 A","Mechanical Service Life (Operating Cycles) Of Contactor Typical":"10 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5a3723d45a53d8566e5b74156cf98d62.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=27991&mlfb=3RA2120-4AD26-0FB4","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RA2120-4AD26-0FB4/alternatives.json"},"ai":{"faq":[{"question":"What is the 3RA2120-4AD26-0FB4 used for?","answer":"It is a direct-on-line (DOL) motor starter (cite:) — a factory-assembled combination of a contactor and overload relay in one unit. It starts and stops a three-phase motor under overload protection, sized for loads up to 16 A at 400 V AC-3 (cite:) with a Class 10 trip curve (cite:)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2120-4AD26-0FB4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2120-4AD26-0FB4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}