{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2210-0ED15-2AP0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2210-0ED15-2AP0","canonicalUrl":"https://aoctrl.com/siemens/3RA2210-0ED15-2AP0","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2210-0ED15-2AP0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2210-0ED15-2AP0 reversing starter, S00 frame, 90 kW at 400 V AC-3, Class 10 trip, screw terminals, snaps onto 60 mm busbars.","salesMarkdown":"## Reversing starter for 60 mm busbar systems The 3RA2210-0ED15-2AP0: It ships as a pre-assembled unit containing the 3RT2015-1AP02 contactor and the 3RA1921-1DA00 link module, so the reversing interlock is factory-set and the wiring between the two contactors is internal. ## Trip Class 10 and thermal coordination This coordinates with standard motor starting profiles — a pump or fan that accelerates within 5–8 seconds stays under the curve, while a stalled rotor condition clears fast enough to protect the winding insulation. The operating temperature range is -20 to +60 °C, with the same range for temperature compensation — the thermal model adjusts the trip threshold as the ambient in the panel rises, so you don't get nuisance trips on a hot afternoon or fail to protect on a cold startup. ## Mounting dimensions and clearance The unit measures 155 mm deep, 90 mm wide, and 204 mm tall. Mounting is vertical only, and the clearance requirements are specific: 50 mm upwards, 32 mm forwards, 10 mm downwards, 10 mm at the side, and 0 mm backwards — the back face sits flush against the busbar system. The main circuit uses screw-type terminals, which is the standard for panel builders who prefer a torque-controlled connection over spring-cage for high-current reversing circuits. The S00 frame size keeps the footprint compact enough for a 600 mm wide panel to carry multiple reversing starters side by side.","metaTitle":"Siemens 3RA2210-0ED15-2AP0 SIRIUS Reversing Starter, 90 kW","metaDescription":"Siemens 3RA2210-0ED15-2AP0 SIRIUS reversing starter, S00 frame, 90 kW at 400 V AC-3, Class 10. Snaps onto 60 mm busbars. Current production — quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"155 mm","Width":"90 mm","title":"3RA2210-0ED15-2AP0","Height":"204 mm","Upwards":"50 mm","Forwards":"32 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"10 mm","Rated Value":"690 V","description":"Load feeder fuseless, Reversing duty 400 V AC, Size S00 0.28...0.40 A 230 V AC screw terminal for 60 mm busbar systems (also fulfills type of coordination 1) Type of coordination 2, Iq = 150 kA 1 NC (contactor)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"for snapping onto 60 mm busbar systems","Mounting Position":"vertical","PROFIsafe protocol":"No","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Product Designation":"Reversing starter","Size Of Load Feeder":"S00","PROFINET IO protocol":"No","at 400 V rated value":"90 kW","at 480 V rated value":"0.4 A","at 50 Hz rated value":"230 ... 230 V","at 60 Hz rated value":"230 ... 230 V","at 600 V rated value":"0.4 A","Design Of The Product":"for 60 mm busbars","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","Of The Supplied Contactor":"3RT2015-1AP02","Of The Supplied Link Module":"3RA1921-1DA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","at AC-3 at 400 V rated value":"0.4 A","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.4 A","Design Of The Overload Release":"thermal (bimetallic)","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","of the supplied RS assembly kit":"3RA2913-1DB1","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0EA10","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Without Load Current Share Typical":"4.2 W","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2 W","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"4.2 VA","protocol is supported AS-Interface protocol":"No","with high demand rate according to SN 31920":"73 %","reference code according to IEC 81346-2:2019":"Q","shock resistance according to IEC 60068-2-27":"6g / 11 ms","Type Of Voltage Of The Control Supply Voltage":"AC","at 400 V according to IEC 60947-4-1 rated value":"150 000 A","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Mechanical Service Life (Operating Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"5.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/54dd185da60c870eefc33f2d07aada66.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=168295&mlfb=3RA2210-0ED15-2AP0"},"ai":{"faq":[{"question":"What are the key ratings for the 3RA2210-0ED15-2AP0?","answer":"The operating temperature range is -20 to +60 °C."},{"question":"How do I get pricing and availability for the 3RA2210-0ED15-2AP0?","answer":"Submit an RFQ against your BOM quantity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2210-0ED15-2AP0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2210-0ED15-2AP0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}