{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2215-0BA15-2AK6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2215-0BA15-2AK6","canonicalUrl":"https://aoctrl.com/siemens/3RA2215-0BA15-2AK6","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2215-0BA15-2AK6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2215-0BA15-2AK6, non-fused reversing motor starter, size S00, Class 10, 690 V AC-3, 50/60 Hz, snap-on DIN rail mount.","salesMarkdown":"The Siemens SIRIUS 3RA2215-0BA15-2AK6 is a non-fused reversing motor starter in size S00, designed for switching and protecting three-phase motors up to 690 V AC-3. It integrates a 3RT2015-1AK62 contactor, a 3RV2011-0BA15 circuit-breaker, and a thermal bimetallic overload relay with Class 10 trip characteristic — meaning it will trip within 10 seconds at 7.2× rated current, matching standard motor starting curves for pumps, fans, and light conveyors. Rated at 690 V AC-3, this starter handles the common 400 V and 480 V motor circuits found across European and North American panels. The 50/60 Hz operating frequency covers both mains standards without derating. Class 10 overload protection is the standard choice for standard- and high-efficiency induction motors — it allows the inrush during start without nuisance tripping, but clears quickly on a jam. The reversing contactor arrangement (two contactors mechanically interlocked) means the motor can be driven forward and reverse without external interlocking relays. The supplied link module 3RA1921-1DA00 pre-wires the power circuit between the contactors and the circuit-breaker, reducing panel wiring time. Mounting position is vertical only. Dimensions: 170 mm high, 90 mm wide, 97.1 mm deep. Clearance requirements: 20 mm upward, 10 mm downward, 9 mm to the side, 0 mm forward or backward — so it fits tightly in a standard 200 mm deep enclosure with room for wiring ducts. Main contact terminals accept 0.5 to 4 mm² solid or stranded, or 2x (0.75 to 2.5 mm²) for paralleled feeds. AWG equivalents: 2x (20–16), 2x (18–14), or 2x 12. The auxiliary switch option is available as a product extension, so you can add a feedback contact for PLC status monitoring.","metaTitle":"Siemens 3RA2215-0BA15-2AK6 SIRIUS Reversing Starter","metaDescription":"Siemens SIRIUS 3RA2215-0BA15-2AK6 non-fused reversing motor starter, size S00, Class 10, 690 V, 50/60 Hz. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Depth":"97.1 mm","Width":"90 mm","title":"3RA2215-0BA15-2AK6","Height":"170 mm","Upwards":"20 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"690 V","description":"FUSELESS MOTOR STARTER REVERSING OPERATION 600V AC SZ S00 0.14-0.2A 110/120V AC 50/60HZ SCREW CONNECTION FOR SCREW MOUNTING OR 35 MM RAIL-MOUNTING TYPE OF COORDINATION 2 IQ = 150 KA ALSO FULFILLS TYPE OF COORDINATION 1 1NO+1NC (MSP) 1NC (PER CONTACTOR)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Snap-mounted to DIN rail or screw-mounted with additional push-in lug","Mounting Position":"vertical","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Degree Of Pollution":"3","Product Designation":"non-fused motor starter 3RA2","Size Of Load Feeder":"S00","at 400 V rated value":"60 W","at 50 Hz rated value":"93.5 ... 121 V","at 500 V rated value":"60 W","at 60 Hz rated value":"96 ... 132 V","at 690 V rated value":"90 W","Design Of The Product":"reversing starter","Of The Supplied Contactor":"3RT2015-1AK62","For Main Contacts Stranded":"0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)","Of The Supplied Link Module":"3RA1921-1DA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","Design Of The Overload Release":"thermal (bimetallic)","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","at AWG cables for main contacts":"2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0BA15","Product Extension Auxiliary Switch":"Yes","Surge Voltage Resistance Rated Value":"6 kV","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"4.8 VA","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"6g / 11 ms","at 400 V according to IEC 60947-4-1 rated value":"153 000 A","at 500 V according to IEC 60947-4-1 rated value":"100 000 A","at 690 V according to IEC 60947-4-1 rated value":"100 000 A","operational current at AC-3 at 400 V rated value":"0.2 A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Mechanical Service Life (Switching Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"2.6 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.14 ... 0.2 A","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9e488426c2401d4f35210532a6da528b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=416029&mlfb=3RA2215-0BA15-2AK6"},"ai":{"faq":[{"question":"What is 3RA2215-0BA15-2AK6's listed depth?","answer":"The depth is 97.1 mm."},{"question":"What is 3RA2215-0BA15-2AK6's listed width?","answer":"The width is 90 mm."},{"question":"Will 3RA2215-0BA15-2AK6 drop into a panel that was specified around 3RV6011-0CA10 without rewiring?","answer":"No — 3RV6011-0CA10 is a circuit-breaker only, not a complete reversing starter. The 3RA2215-0BA15-2AK6 is a pre-assembled combination starter with its own integrated circuit-breaker (3RV2011-0BA15) and contactor (3RT2015-1AK62). Panel wiring differs entirely."},{"question":"What compliance documentation does this brand provide for 3RA2215-0BA15-2AK6?","answer":"Siemens SIRIUS components typically carry CE, UL, CSA, and CCC approvals, plus RoHS and REACH declarations. The surge voltage resistance is rated at 6 kV, and the degree of pollution is 3. Specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2215-0BA15-2AK6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2215-0BA15-2AK6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}