{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2225-0HB23-0AP6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2225-0HB23-0AP6","canonicalUrl":"https://aoctrl.com/siemens/3RA2225-0HB23-0AP6","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2225-0HB23-0AP6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2225-0HB23-0AP6, non-fused reversing motor starter, size S0/S00, Class 10, 690 V, snap-on 35 mm DIN rail.","salesMarkdown":"## What this SIRIUS reversing starter is The Siemens 3RA2225-0HB23-0AP6 is a non-fused reversing motor starter from the SIRIUS 3RA2 family, combining a contactor and overload relay in one package for forward/reverse control of a three-phase motor. It ships as a complete assembly: the supplied contactor is a 3RT2023-1AP60, the link module is 3RA2921-1AA00, the busbar adapter is 3RA2922-1AA00, and the reversing (RH) assembly kit is 3RA2923-1BB1 — everything needed to drop it on the rail and wire it up. Dimensions are 90 mm wide, 120 mm deep, 265 mm tall, with clearance requirements: 30 mm upwards, 10 mm forwards, 10 mm downwards, 9 mm at the side, and zero backwards — tight enough for a crowded panel if you plan the gland plate. Main contact wiring accepts stranded 1 to 10 mm² or 2x (2.5 to 6 mm²); AWG equivalents are 2x (16 to 12) or 2x (14 to 8). This is a stocked catalog item in the SIRIUS 3RA2 line, sourced through independent distribution channels.","metaTitle":"Siemens 3RA2225-0HB23-0AP6 SIRIUS Reversing Starter","metaDescription":"Siemens 3RA2225-0HB23-0AP6 SIRIUS non-fused reversing motor starter, size S0/S00, Class 10 thermal overload, 690 V, snap-on DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Depth":"120 mm","Width":"90 mm","Height":"265 mm","Upwards":"30 mm","Forwards":"10 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"snap-on fastening on 35 mm standard rail","Mounting Position":"vertical","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Degree Of Pollution":"3","Product Designation":"non-fused motor starter 3RA2","Size Of Load Feeder":"S0","at 400 V rated value":"180 W","at 50 Hz rated value":"176 ... 242 V","at 500 V rated value":"250 W","at 60 Hz rated value":"192 ... 264 V","at 690 V rated value":"370 W","Design Of The Product":"reversing starter","Of The Supplied Contactor":"3RT2023-1AP60","For Main Contacts Stranded":"1 ... 10 mm², 2x (2.5 ... 6 mm²)","Of The Supplied Link Module":"3RA2921-1AA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","Substance Prohibitance (Date)":"03/01/2017","Design Of The Overload Release":"thermal (bimetallic)","Of The Supplied Busbar Adapter":"3RA2922-1AA00","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","at AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","of the supplied RH assembly kit":"3RA2923-1BB1","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0HA15","Product Extension Auxiliary Switch":"Yes","Surge Voltage Resistance Rated Value":"6 kV","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"7.2 VA","number of NC contacts for auxiliary contacts":"3","number of NO contacts for auxiliary contacts":"3","shock resistance according to IEC 60068-2-27":"6g / 11 ms","Of The Supplied Standard Mounting Rail Adapter":"3RA2922-1AA00","at 400 V according to IEC 60947-4-1 rated value":"153 000 A","operational current at AC-3 at 400 V rated value":"0.6 A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Inductive Power Factor With The Holding Power Of The Coil":"0.28","Mechanical Service Life (Switching Cycles) Of Contactor Typical":"10 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"10.4 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"1 ... 6 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=306542&mlfb=3RA2225-0HB23-0AP6","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RA2225-0HB23-0AP6/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RA2225-0HB23-0AP6?","answer":"This reversing starter is sourced to order against an RFQ through independent distribution. Submit a request for current availability and pricing."},{"question":"Can 3RA2225-0HB23-0AP6 be used for a 0.75 A motor?","answer":"The overload relay is thermal bimetallic with a Class 10 trip; verify the specific current setting range of the supplied overload block against your motor's full-load amps. The contactor and overload are rated for the S0/S00 feeder size, which typically covers fractional-horsepower motors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2225-0HB23-0AP6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2225-0HB23-0AP6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}