{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2316-8XB30-1AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2316-8XB30-1AH0","canonicalUrl":"https://aoctrl.com/siemens/3RA2316-8XB30-1AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2316-8XB30-1AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS reversing contactor assembly, S00 size, 4 kW at 400 V AC-3, 7.6 A at 480 V, 5.5 kW at 690 V, includes two 3RT2016-1AH02 contactors, screw-type terminals, 68 x 90 x 73 mm, DIN rail mount.","salesMarkdown":"## Panel fit and mounting flexibility The 3RA2316-8XB30-1AH0: This assembly mounts on a 35 mm standard DIN rail using either the screw or snap-on method — no adapter plate needed. The S00 footprint measures 68 mm high by 90 mm wide by 73 mm deep, so it fits tight subpanels where depth is the constraint. Mounting position is flexible: you can rotate it ±180° on a vertical surface or tilt it forward/backward by ±22.5°, which helps when routing wires around gland plates or other components. ## Wire termination and environmental limits Both the main current circuit and magnet coil use screw-type terminals. The coil terminals take the same range plus 2x 4 mm² solid. Vibration resistance is rated at 10.5g for 5 ms and 6.6g for 10 ms on both AC and DC axes.","metaTitle":"Siemens 3RA2316-8XB30-1AH0 SIRIUS Reversing Contactor","metaDescription":"Siemens 3RA2316-8XB30-1AH0 SIRIUS reversing contactor assembly, S00 size, 4 kW at 400 V AC-3. Current production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"73 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Width":"90 mm","at AC":"10,5g / 5 ms, 6,6g / 10 ms","at DC":"10,5g / 5 ms, 6,6g / 10 ms","Height":"68 mm","Upwards":"6 mm","Forwards":"6 mm","at 50 Hz":"0.25","at 60 Hz":"0.85 ... 1.1","Backwards":"0 mm","Downwards":"6 mm","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Reversing contactor assembly","Of Contactor Typical":"10 000 000","at 400 V rated value":"4 kW","at 480 V rated value":"7.6 A","at 50 Hz rated value":"48 V","at 500 V rated value":"4 kW","at 60 Hz rated value":"48 V","at 600 V rated value":"9 A","at 690 V rated value":"5.5 kW","For Main Current Circuit":"screw-type terminals","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","1 Of The Supplied Contactor":"3RT2016-1AH02","2 Of The Supplied Contactor":"3RT2016-1AH02","at AC-4 at 400 V rated value":"4 kW","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14)","of the supplied RH assembly kit":"3RA2913-2AA1","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Product Function Bus Communication":"Yes","With Type Of Assignment 2 Required":"gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-3 maximum":"750 1/h","With Type Of Coordination 1 Required":"gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"< 1 error per 100 million operating cycles","with low demand rate according to SN 31920":"40 %","protocol is supported AS-Interface protocol":"No","with high demand rate according to SN 31920":"75 %","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","product function control circuit interface with IO link":"No","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a27f4fee0599641c68ccae84cf168670.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=266473&mlfb=3RA2316-8XB30-1AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RA2316-8XB30-1AH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RA2316-8XB30-1AH0?","answer":"Submit an RFQ through this page."},{"question":"What is the mechanical life of this reversing contactor assembly?","answer":"It is rated for 10,000,000 operating cycles typical. This applies to the contactor mechanism under normal switching conditions — actual life in reversing duty depends on the load current and switching frequency."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2316-8XB30-1AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2316-8XB30-1AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}