{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2416-8XF31-2AP6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2416-8XF31-2AP6","canonicalUrl":"https://aoctrl.com/siemens/3RA2416-8XF31-2AP6","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2416-8XF31-2AP6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2416-8XF31-2AP6 contactor assembly for star-delta (wye-delta) start, size S00, 7.5 kW at 400 V, spring-loaded terminals, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Star-delta starter assembly — what ships in the box This 3RA2416-8XF31-2AP6 is a pre-assembled SIRIUS contactor assembly for star-delta (wye-delta) starting of three-phase motors. It ships with three contactors: two 3RT2017-2AP61 and one 3RT2015-2AP61, plus the RS assembly kit 3RA2913-2BB2. Maximum AC-3 operating voltage is 690 V. ## DIN rail fit and panel clearance The S00 frame measures 84 mm high, 135 mm wide, and 145 mm deep — that depth includes the spring-loaded terminals, so plan for wire bend radius behind the rail. Clearance requirements: 6 mm upwards, forwards, downwards, and to the sides; 0 mm backwards (the back of the assembly sits flush against the mounting surface). ## Terminations and wiring All main circuit, auxiliary, and control circuit connections use spring-loaded terminals — no screw torquing needed, but the cage mechanism demands a solid or ferruled stranded conductor. The magnet coil also terminates on spring-type terminals. For AWG, main contacts accept 1x (20... 12). The spring clamp holds the full cross-section without cold flow — wire the ferrule fully seated before closing the lever. ## Duty cycle and mechanical endurance Maximum switching rate in AC-3 duty is 1 000 operations per hour. Typical mechanical life of the contactor is 10 000 000 cycles — this is the no-load mechanical endurance; electrical life under load will be lower and depends on the motor current and switching frequency. Shock resistance: 10.5 g for 5 ms and 6.6 g for 10 ms, tested at both AC and DC.","metaTitle":"Siemens 3RA2416-8XF31-2AP6 SIRIUS Star-Delta Starter","metaDescription":"Siemens 3RA2416-8XF31-2AP6 SIRIUS contactor assembly for star-delta start. Rated 7.5 kW at 400 V, 10.3 kW at 500 V. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"145 mm","Width":"135 mm","Height":"84 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a056732129391f82f65af322832c991b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=356763&mlfb=3RA2416-8XF31-2AP6","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RA2416-8XF31-2AP6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2416-8XF31-2AP6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2416-8XF31-2AP6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}