{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2425-8XF32-2AC2","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2425-8XF32-2AC2","canonicalUrl":"https://aoctrl.com/siemens/3RA2425-8XF32-2AC2","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2425-8XF32-2AC2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2425-8XF32-2AC2 contactor assembly for star-delta (wye-delta) start, 15 kW at 400 V, 24 VAC 50/60 Hz coil, spring-type terminals, Size S0, DIN rail mount.","salesMarkdown":"## Star-delta starter kit — what's in the box The 3RA2425-8XF32-2AC2 is a pre-assembled SIRIUS contactor assembly for star-delta (wye-delta) motor starting — three contactors and the RS timing relay on a common mounting plate, wired and tested at the factory. The kit ships with two 3RT2026-2AC20 contactors (line and star) and one 3RT2024-2AC20 (delta), plus the 3RA2923-2BB2 RS assembly kit — no separate ordering of individual contactors needed. ## Panel fit and mounting flexibility Size S0 footprint: 114 mm high, 135 mm wide, 171 mm deep — screw-fix or snap-on onto 35 mm standard DIN rail, with mounting position adjustable ±180° rotation and ±22.5° tilt on a vertical surface. Clearance distances: 6 mm upwards, forwards, downwards, and sideways; 0 mm backwards — the assembly sits flush against the back panel, saving depth in shallow enclosures. ## Wiring and termination — spring terminals throughout Main contact AWG range is 1x (18... 8) — the spring clamp holds the full conductor cross-section without cold flow under thermal cycling. ## Environmental limits and shock rating Shock resistance: 11.8 g / 5 ms and 7.4 g / 10 ms in AC operation; 15 g / 5 ms and 10 g / 10 ms in DC — the assembly holds contact closure under moderate vibration on conveyor and pump applications. RoHS compliance date 10/01/2009 — the assembly meets EU substance restrictions for industrial equipment shipped into regulated markets.","metaTitle":"Siemens 3RA2425-8XF32-2AC2 SIRIUS Star-Delta Starter","metaDescription":"Siemens SIRIUS 3RA2425-8XF32-2AC2 contactor assembly for star-delta motor starting. Rated 15 kW at 400 V, 24 VAC coil, spring terminals.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"171 mm","Width":"135 mm","Height":"114 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5fb9cad3fe35e3f285dfd7c64fb160a7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=97953&mlfb=3RA2425-8XF32-2AC2","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RA2425-8XF32-2AC2/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2425-8XF32-2AC2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2425-8XF32-2AC2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}