{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA6120-0BP30","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA6120-0BP30","canonicalUrl":"https://aoctrl.com/siemens/3RA6120-0BP30","factsUrl":"https://aoctrl.com/api/mcp/products/3RA6120-0BP30","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS compact direct starter, 3RA6120-0BP30, 53 kA at 400 V, adjustable trip class 10/20, 45 x 170 x 165 mm, plug-in without terminals.","salesMarkdown":"## Panel fit — 45 mm wide, 165 mm deep, screw-and-snap DIN rail The 3RA6120-0BP30 measures 45 mm wide by 170 mm tall by 165 mm deep — it takes two standard DIN-rail modules and leaves room for gland plates in a 200 mm deep enclosure. Fastening is screw and snap-on mounting to a horizontal standard mounting rail, so it wires up clean without extra brackets. The main circuit connects via plug-in without terminals — no screw torque to check, just seat the contact blades and latch. ## Breaking capacity and motor protection — 53 kA at 400 V, adjustable trip class Rated 53 kA at 400 V, this compact starter coordinates with upstream MCCBs and fuses up to that fault level — the SCCR headroom covers most 400 V distribution panels without a series-rating sticker. Trip class is adjustable between CLASS 10 and CLASS 20 (IEC 60947-6-2), so you set the overload relay to match the motor start profile: CLASS 10 for short acceleration times on pumps and fans, CLASS 20 for high-inertia loads like conveyors or crushers. Continuous operation per IEC 60947-6-2 means the thermal memory tracks motor heating during repeated starts — no nuisance tripping on a restart after a brief stop. No direct pin-compatible replacement exists — this is the active SIRIUS compact starter for 400 V motor circuits up to 370 W at 400 V.","metaTitle":"Siemens 3RA6120-0BP30 SIRIUS Compact Starter, 53 kA at 400 V","metaDescription":"Siemens 3RA6120-0BP30 SIRIUS compact direct starter, 53 kA breaking capacity at 400 V, adjustable trip class 10/20, 45 mm wide, active production, quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"165 mm","Width":"45 mm","at DC":"110 ... 240 V","title":"3RA6120-0BP30","Height":"170 mm","at 400 V":"53 kA","at 50 Hz":"110 ... 240 V","at 60 Hz":"110 ... 240 V","Trip Class":"CLASS 10 and 20 adjustable","Recommended":"vertical, on horizontal standard mounting rail","description":"SIRIUS Compact load feeder DOL starter 690 V 110...240 V AC/DC 50...60 Hz 0.32...1.25 A IP20 Connection main circuit: plug-in, without terminals Connection auxiliary circuit: plug-in, without terminals","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","at AC maximum":"6 W","at DC maximum":"5.1 W","During Storage":"-55 ... +80 °C","number of LEDs":"2","Type Of Voltage":"AC/DC","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","IO-Link protocol":"No","Shock Resistance":"a=60 m/s2 (6g) with 10 ms per 3 shocks in all axes","Mounting Position":"any","at DC rated value":"240 V","Product Brand Name":"SIRIUS","Type Of Assignment":"continous operation according to IEC 60947-6-2","Degree Of Pollution":"3","Product Designation":"compact starter","Vibration Resistance":"f= 4 ... 5.8 Hz, d= 15 mm; f= 5.8 ... 500 Hz, a= 20 m/s²; 10 cycles","at 400 V rated value":"370 W","at 480 V rated value":"1.25 A","at 50 Hz rated value":"240 V","at 500 V rated value":"3 kA","at 600 V rated value":"1.25 A","at 690 V rated value":"3 kA","AS-Interface protocol":"No","Design Of The Product":"direct starter","For Main Current Circuit":"plug-in without terminals","at 460/480 V rated value":"0.5 hp","at 575/600 V rated value":"0.5 hp","at AC at 400 V rated value":"1.25 A","NO-Load Switching Frequency":"3 600 1/h","Of The Main Contacts Typical":"10 000 000","at AC in hot operating state":"0.1 W","at AC-3 at 400 V rated value":"0.37 kW","Of Auxiliary Contacts Typical":"10 000 000","Substance Prohibitance (Date)":"05/01/2012","Insulation Voltage Rated Value":"690 V","at DC-13 at 6 A at 24 V typical":"30 000","at AC-15 at 6 A at 230 V typical":"200 000","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"plug-in without terminals","Of The Signaling Contacts Typical":"10 000 000","Between Main And Auxiliary Circuit":"400 V","Design Of Short-Circuit Protection":"electromagnetic","Product Extension Auxiliary Switch":"Yes","Product Function Bus Communication":"No","Relative Humidity During Operation":"10 ... 90 %","Without Load Current Share Typical":"6 W","Surge Voltage Resistance Rated Value":"6 000 V","Between Control And Auxiliary Circuit":"300 V","at AC in hot operating state per pole":"0.03 W","Between Auxiliary And Auxiliary Circuit":"250 V","due to burst according to IEC 61000-4-4":"4 kV main contacts, 2 kV auxiliary contacts","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","Formula For Making Capacity Limit Current":"38.4 x Ie","Product Function Short Circuit Protection":"Yes","Supply voltage required Auxiliary voltage":"No","with low demand rate according to SN 31920":"40 %","Formula For Breaking Capacity Limit Current":"32 x Ie","at AC-41 according to IEC 60947-6-2 maximum":"750 1/h","at AC-43 according to IEC 60947-6-2 maximum":"250 1/h","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","operating voltage at AC-3 rated value maximum":"690 V","electrostatic discharge according to IEC 61000-4-2":"8 kV","contact rating of auxiliary contacts according to UL":"contacts 21-22, 13-14, 43-44 Q600 / A600, contacts 77-78 R300 / B300, contacts 95-96-98 R300 / D300","Product Component Removable Terminal For Main Circuit":"Yes","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","product function control circuit interface with IO link":"No","conducted HF interference emissions according to CISPR11":"150 kHz ... 30 MHz Class A","field-bound HF interference emission according to CISPR11":"30 ... 1000 MHz Class A","operational current of auxiliary contacts at AC-12 maximum":"10 A","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Product Function Control Circuit Interface To Parallel Wiring":"Yes","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.32 ... 1.25 A","number of NO contacts of instantaneous short-circuit trip unit for signaling contact":"1","For Short-Circuit Protection Of The Signaling Switch Of The Overload Release Required":"4A gL/gG/400V","number of CO contacts of the current-dependent overload release for signaling contact":"1","For Short-Circuit Protection Of The Signaling Switch Of The Short-Circuit Release Required":"6A gL/gG/400V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/98e3bb49977dbdfbff5165e4c96814ed.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=223865&mlfb=3RA6120-0BP30"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA6120-0BP30","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA6120-0BP30 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}