{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA6120-2AB32","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA6120-2AB32","canonicalUrl":"https://aoctrl.com/siemens/3RA6120-2AB32","factsUrl":"https://aoctrl.com/api/mcp/products/3RA6120-2AB32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA6120-2AB32 compact starter, direct starter, 24 V DC/AC control, 53 kA breaking capacity at 400 V, adjustable trip class 10 and 20, spring-loaded terminals, 45 mm wide.","salesMarkdown":"The Siemens 3RA6120-2AB32 is a SIRIUS compact starter — a direct-on-line motor starter that combines a contactor and overload relay in one 45 mm wide package. It's meant for continuous duty per IEC 60947-6-2, so it's sized for running a motor load, not just jogging it. The 24 V DC/AC control voltage means it drops into a standard 24 V control circuit without a separate transformer tap. At 480 V the interrupting rating drops to 0.4 A, and at 690 V it's 3 kA, so match the rating to your available fault current. The adjustable trip class — selectable between CLASS 10 and CLASS 20 — lets you set the overload curve to the motor's thermal capacity: CLASS 10 for pumps and fans that start unloaded, CLASS 20 for high-inertia loads like centrifuges or crushers that need a longer acceleration ramp.","metaTitle":"Siemens 3RA6120-2AB32 SIRIUS Compact Starter, 24 VDC, 53 kA","metaDescription":"Siemens 3RA6120-2AB32 SIRIUS compact starter. 24 VDC control, 53 kA breaking capacity at 400 V, adjustable trip class 10/20. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"165 mm","Solid":"2x (0.25 ... 1.5 mm²)","Width":"45 mm","at DC":"24 ... 24 V","title":"3RA6120-2AB32","Height":"191 mm","at 400 V":"53 kA","at 50 Hz":"24 ... 24 V","at 60 Hz":"24 V","Trip Class":"CLASS 10 and 20 adjustable","Recommended":"vertical, on horizontal standard DIN rail","description":"SIRIUS Compact load feeder DOL starter 690 V 24 V AC/DC 50...60 Hz 0.1...0.4 A IP20 Connection main circuit: Spring-type terminal Connection auxiliary circuit: Spring-type terminal","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","at AC maximum":"2.8 W","at DC maximum":"2.9 W","During Storage":"-55 ... +80 °C","number of LEDs":"2","Type Of Voltage":"AC/DC","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","IO-Link protocol":"No","Shock Resistance":"a=60 m/s2 (6g) with 10 ms per 3 shocks in all axes","Mounting Position":"any","at DC rated value":"24 V","Product Brand Name":"SIRIUS","Type Of Assignment":"continous operation according to IEC 60947-6-2","Degree Of Pollution":"3","Product Designation":"compact starter","Vibration Resistance":"f= 4 ... 5.8 Hz, d= 15 mm; f= 5.8 ... 500 Hz, a= 20 m/s²; 10 cycles","at 400 V rated value":"90 W","at 480 V rated value":"0.4 A","at 50 Hz rated value":"24 V","at 500 V rated value":"3 kA","at 60 Hz rated value":"24 V","at 600 V rated value":"0.4 A","at 690 V rated value":"3 kA","AS-Interface protocol":"No","Design Of The Product":"direct starter","For Main Current Circuit":"spring-loaded terminals","at AC at 400 V rated value":"0.4 A","NO-Load Switching Frequency":"3 600 1/h","Of The Main Contacts Typical":"10 000 000","at AC in hot operating state":"0.01 W","at AC-3 at 400 V rated value":"0.09 kW","Of Auxiliary Contacts Typical":"10 000 000","Substance Prohibitance (Date)":"05/01/2012","Insulation Voltage Rated Value":"690 V","at DC-13 at 6 A at 24 V typical":"30 000","at AC-15 at 6 A at 230 V typical":"200 000","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"spring-loaded terminals","Of The Signaling Contacts Typical":"10 000 000","Between Main And Auxiliary Circuit":"400 V","Design Of Short-Circuit Protection":"electromagnetic","Product Extension Auxiliary Switch":"Yes","Product Function Bus Communication":"No","Relative Humidity During Operation":"10 ... 90 %","Without Load Current Share Typical":"2.9 W","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (24 ... 16)","Between Control And Auxiliary Circuit":"300 V","at AC in hot operating state per pole":"0.01 W","Between Auxiliary And Auxiliary Circuit":"250 V","due to burst according to IEC 61000-4-4":"4 kV main contacts, 2 kV auxiliary contacts","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Formula For Making Capacity Limit Current":"120 x Ie","Product Function Short Circuit Protection":"Yes","Supply voltage required Auxiliary voltage":"No","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.25 ... 1.5 mm²)","Formula For Limit Current Breaking Capacity":"100 x Ie","at AC-41 according to IEC 60947-6-2 maximum":"750 1/h","at AC-43 according to IEC 60947-6-2 maximum":"250 1/h","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","operating voltage at AC-3 rated value maximum":"690 V","electrostatic discharge according to IEC 61000-4-2":"8 kV","contact rating of auxiliary contacts according to UL":"contacts 21-22, 13-14, 43-44 Q600 / A600, contacts 77-78 R300 / B300, contacts 95-96-98 R300 / D300","Product Component Removable Terminal For Main Circuit":"Yes","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","product function control circuit interface with IO link":"No","conducted HF interference emissions according to CISPR11":"150 kHz ... 30 MHz Class A","field-bound HF interference emission according to CISPR11":"30 ... 1000 MHz Class A","operational current of auxiliary contacts at AC-12 maximum":"10 A","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Product Function Control Circuit Interface To Parallel Wiring":"Yes","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.1 ... 0.4 A","number of NO contacts of instantaneous short-circuit trip unit for signaling contact":"1","For Short-Circuit Protection Of The Signaling Switch Of The Overload Release Required":"4A gL/gG/400V","number of CO contacts of the current-dependent overload release for signaling contact":"1","For Short-Circuit Protection Of The Signaling Switch Of The Short-Circuit Release Required":"6A gL/gG/400V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fa921dec66c3c4d9e150a237cc9c2b28.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=385103&mlfb=3RA6120-2AB32"},"ai":{"faq":[{"question":"What is the trip class of 3RA6120-2AB32?","answer":"It's adjustable between CLASS 10 and CLASS 20. CLASS 10 trips faster for standard-start loads; CLASS 20 gives more time for high-inertia starts. You set it with the dial on the overload block."},{"question":"Where can I buy 3RA6120-2AB32 available via RFQ confirmation?","answer":"This part is sourced to order against your RFQ. Availability and pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA6120-2AB32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA6120-2AB32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}