{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA6250-0EP30","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA6250-0EP30","canonicalUrl":"https://aoctrl.com/siemens/3RA6250-0EP30","factsUrl":"https://aoctrl.com/api/mcp/products/3RA6250-0EP30","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA6250-0EP30 compact reversing starter, 32 A at 400 V AC, 53 kA breaking capacity, adjustable trip Class 10/20, 110-240 V AC/DC control, screw and snap-on DIN rail mounting.","salesMarkdown":"## Breaking capacity and motor protection The 3RA6250-0EP30: The adjustable trip class (Class 10 and 20,) lets you match the thermal overload curve to the motor start profile: Class 10 for faster starts like pumps, Class 20 for high-inertia loads like conveyors or fans. Continuous duty rating per IEC 60947-6-2 at 32 A in AC-3 means it handles motor switching loads at that current without derating for continuous operation. At 480 V it's also rated 32 A; horsepower equivalents are 7.5 hp at 200/208 V, 10 hp at 220/230 V, and 20 hp at 460/480 V (-). ## Panel fit and mounting constraints Dimensions 170 x 90 x 165 mm — the 90 mm width is three standard 18 mm DIN module spaces, so plan the DIN rail allocation accordingly. The main circuit uses plug-in connections without terminals — the starter plugs into a base, so the wiring stays in the panel when swapping the unit. Control supply is AC/DC 110-240 V at 50/60 Hz. Power dissipation is 5.2 W AC max and 5.8 W DC max — account for this in the enclosure thermal budget. ## Environmental and vibration qualification Operates from -20 to +60 °C; storage and transport range is -55 to +80 °C. Shock resistance is 6g with 10 ms pulses, three shocks per axis. Vibration tested at 4-5.8 Hz with 15 mm displacement and 5.8-500 Hz at 20 m/s² for 10 cycles — suitable for panel mounting on machinery subject to moderate vibration. Pollution degree 3 confirms it's rated for conductive pollution environments typical in industrial panels.","metaTitle":"Siemens 3RA6250-0EP30 SIRIUS Reversing Starter, 32 A, 53 kA","metaDescription":"Siemens 3RA6250-0EP30 SIRIUS compact reversing starter. Rated 32 A at 400 V AC, 53 kA breaking capacity, adjustable Class 10/20.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"165 mm","Width":"90 mm","at DC":"110 ... 240 V","title":"3RA6250-0EP30","Height":"170 mm","at 400 V":"53 kA","at 50 Hz":"110 ... 240 V","at 60 Hz":"110 ... 240 V","Trip Class":"CLASS 10 and 20 adjustable","Recommended":"vertical, on horizontal standard DIN rail","description":"SIRIUS Compact load feeder Reversing starter 400 V 110...240 V AC/DC 50...60 Hz 8...32 A IP20 Connection main circuit: plug-in, without terminals Connection control circuit: plug-in, without terminals","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","at AC maximum":"5.2 W","at DC maximum":"5.8 W","During Storage":"-55 ... +80 °C","number of LEDs":"3","Type Of Voltage":"AC/DC","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","IO-Link protocol":"No","Shock Resistance":"a=60 m/s2 (6g) with 10 ms per 3 shocks in all axes","Mounting Position":"any","at DC rated value":"240 V","Product Brand Name":"SIRIUS","Type Of Assignment":"continous operation according to IEC 60947-6-2","Degree Of Pollution":"3","Product Designation":"compact starter","Vibration Resistance":"f= 4 ... 5.8 Hz, d= 15 mm; f= 5.8 ... 500 Hz, a= 20 m/s²; 10 cycles","at 400 V rated value":"15 000 W","at 480 V rated value":"32 A","at 50 Hz rated value":"240 V","AS-Interface protocol":"No","Design Of The Product":"reversing starter","For Main Current Circuit":"plug-in without terminals","at 200/208 V rated value":"7.5 hp","at 220/230 V rated value":"10 hp","at 460/480 V rated value":"20 hp","at AC at 400 V rated value":"32 A","NO-Load Switching Frequency":"3 600 1/h","Of The Main Contacts Typical":"10 000 000","at AC in hot operating state":"5.4 W","at AC-3 at 400 V rated value":"15 kW","Of Auxiliary Contacts Typical":"10 000 000","Substance Prohibitance (Date)":"05/01/2012","Insulation Voltage Rated Value":"690 V","at DC-13 at 6 A at 24 V typical":"30 000","at AC-15 at 6 A at 230 V typical":"200 000","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"plug-in without terminals","Of The Signaling Contacts Typical":"10 000 000","Between Main And Auxiliary Circuit":"400 V","Design Of Short-Circuit Protection":"electromagnetic","Product Extension Auxiliary Switch":"Yes","Product Function Bus Communication":"No","Relative Humidity During Operation":"10 ... 90 %","Without Load Current Share Typical":"5.8 W","Surge Voltage Resistance Rated Value":"6 000 V","Between Control And Auxiliary Circuit":"300 V","at AC in hot operating state per pole":"1.8 W","Between Auxiliary And Auxiliary Circuit":"250 V","due to burst according to IEC 61000-4-4":"4 kV main contacts, 2 kV auxiliary contacts","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","Formula For Making Capacity Limit Current":"12 x Ie","Product Function Short Circuit Protection":"Yes","Supply voltage required Auxiliary voltage":"No","with low demand rate according to SN 31920":"40 %","Formula For Limit Current Breaking Capacity":"10 x Ie","at AC-41 according to IEC 60947-6-2 maximum":"750 1/h","at AC-43 according to IEC 60947-6-2 maximum":"250 1/h","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"2","operating voltage at AC-3 rated value maximum":"400 V","electrostatic discharge according to IEC 61000-4-2":"8 kV","contact rating of auxiliary contacts according to UL":"contacts 21-22, 13-14, 43-44 Q600 / A600, contacts 77-78 R300 / B300, contacts 95-96-98 R300 / D300","Product Component Removable Terminal For Main Circuit":"Yes","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","product function control circuit interface with IO link":"No","conducted HF interference emissions according to CISPR11":"150 kHz ... 30 MHz Class A","field-bound HF interference emission according to CISPR11":"30 ... 1000 MHz Class A","operational current of auxiliary contacts at AC-12 maximum":"10 A","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Product Function Control Circuit Interface To Parallel Wiring":"Yes","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"8 ... 32 A","number of NO contacts of instantaneous short-circuit trip unit for signaling contact":"1","For Short-Circuit Protection Of The Signaling Switch Of The Overload Release Required":"4A gL/gG/400V","number of CO contacts of the current-dependent overload release for signaling contact":"1","For Short-Circuit Protection Of The Signaling Switch Of The Short-Circuit Release Required":"6A gL/gG/400V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/193e64ea726404bfafc72bdbe38b14f4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=207166&mlfb=3RA6250-0EP30"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RA6250-0EP30 at 400 V?","answer":"53 kA at 400 V — this is the short-circuit breaking capacity for fault coordination in the motor branch circuit. It determines the upstream protective device selectivity requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA6250-0EP30","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA6250-0EP30 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}