{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RB3113-4TE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RB3113-4TE0","canonicalUrl":"https://aoctrl.com/siemens/3RB3113-4TE0","factsUrl":"https://aoctrl.com/api/mcp/products/3RB3113-4TE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RB3113-4TE0 solid-state overload relay, S00 frame size, 16 A thermal current, adjustable trip classes 5E/10E/20E/30E, 690 V rated, contactor-mount, spring-loaded terminals.","salesMarkdown":"## S00 Frame, 16 A Continuous — What Fits Where The 3RB3113-4TE0 is a SIRIUS solid-state overload relay in the S00 frame size — 45 mm wide, 72 mm tall, 90 mm deep. It mounts directly onto a contactor (contactor mounting per), not on DIN rail, so the panel layout needs the contactor footprint first. Spring-loaded terminals on the main current circuit accept 2x 0.25...1.5 mm² solid or stranded wire. Rated thermal current Ith is 16 A at 690 V. The trip classes are adjustable — 5E, 10E, 20E, or 30E. That range lets you match the overload characteristic to the motor start profile: pump starts get 10E, high-inertia loads like fans or crushers get 20E or 30E. The solid-state sensing eliminates the bimetal drift you get with thermal relays — no ambient tracking issues across the -25 to +60 °C compensated range. The auxiliary contact set is rated 2 A at 24 V, 4 A at 120 V, 3 A at 230 V, and 0.55 A at 60 V. These are the switching limits for the trip signal back to the PLC or contactor coil — stay within them or buffer through an interposing relay. ## Trip Classes and Motor Protection Logic The relay trips when motor current exceeds the upper setting value by a factor of 3.5. The lower setting value is the minimum continuous current that keeps the relay reset. Between those boundaries, the selected trip class determines how long the relay holds before opening — 5E for fast-acting protection on short-start motors, 10E for standard IEC motor starts, 20E or 30E for high-inertia loads where start times exceed 10 seconds. Shock resistance is 15g / 11 ms on the main contacts; the signaling contact in the tripped position derates to 9g / 11 ms. Vibration resistance follows IEC 60068-2-27: 1-6 Hz at 15 mm amplitude, 6-500 Hz at 20 m/s², 10 cycles. That covers most rotating machinery environments — the relay is not the weak link in a motor starter on a pump skid or conveyor drive. ## Active Production — Sourced to Order Storage and transport temperature range is -40 to +80 °C. The relay carries a substance prohibitance date of 10/01/2009, which aligns with RoHS compliance — the exact RoHS/REACH declaration can be provided with the quote.","metaTitle":"Siemens 3RB3113-4TE0 SIRIUS Solid-State Overload Relay, 16 A","metaDescription":"Siemens 3RB3113-4TE0 SIRIUS solid-state overload relay, 16 A, S00 frame, adjustable trip classes 5E-30E, 690 V rated. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"tripped\"","Depth":"90 mm","Solid":"2x (0.25 ... 1.5 mm²)","Width":"45 mm","title":"3RB3113-4TE0","Height":"72 mm","Maximum":"IMotor < upper current setting value x 3.5","Minimum":"IMotor > lower current setting value","at 24 V":"2 A","at 60 V":"0.55 A","Per Pole":"0.37 W","at 110 V":"0.3 A","at 120 V":"4 A","at 125 V":"0.3 A","at 220 V":"0.11 A","at 230 V":"3 A","Trip Class":"CLASS 5E, 10E, 20E and 30E adjustable","Rated Value":"690 V","description":"Overload relay 4...16 A Electronic For motor protection Size S00, Class 5...30 Contactor mounting Main circuit: Spring-type terminal Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset Internal ground fault detection","During Storage":"-40 ... +80 °C","Thermal Current":"16 A","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-40 ... +80 °C","Fastening Method":"Contactor mounting","Shock Resistance":"15g / 11 ms","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,25 ... 1,5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"solid-state overload relay","Vibration Resistance":"1-6 Hz, 15 mm; 6-500 Hz, 20 m/s²; 10 cycles","at 480 V rated value":"16 A","at 600 V rated value":"16 A","Size Of Overload Relay":"S00","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-25 ... +60 °C","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Screwdriver Tip":"Pozidriv PZ 2","according to IEC 60068-2-27":"15g / 11 ms; Signaling contact 97 / 98 in position \"Tripped\": 9g / 11 ms","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"electronic","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","for AC motors at 500 V at 50 Hz":"2.2 ... 7.5 kW","for AC motors at 690 V at 50 Hz":"3 ... 11 kW","for remote-reset function at DC":"24 V","For Auxiliary And Control Circuit":"spring-loaded terminals","Between Main And Auxiliary Circuit":"690 V","Relative Humidity During Operation":"10 ... 95 %","With Type Of Assignment 2 Required":"gG: 50 A, J: 60 A","Display Version For Switching Status":"Slide switch","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gG: 50 A, RK5: 60 A","at AWG cables for auxiliary contacts":"1x (24 ... 16), 2x (24 ... 16)","for 3-phase motors at 400 V at 50 Hz":"2.2 ... 7.5 kW","Between Auxiliary And Auxiliary Circuit":"300 V","due to burst according to IEC 61000-4-4":"2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Finely Stranded Without Core End Processing":"2x (0.25 ... 1.5 mm²)","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","operational current at AC-3e at 400 V rated value":"16 A","Size Of Contactor Can Be Combined Company-Specific":"S00","electrostatic discharge according to IEC 61000-4-2":"6 kV contact discharge / 8 kV air discharge","Type Of Voltage Supply Via Input/Output Link Master":"No","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Response Time Of The Grounding Protection In Settled State":"1 000 ms","Response Value Current Of The Grounding Protection Minimum":"0.75 x IMotor","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes","power loss [W] for rated value of the current at AC in hot operating state":"1.1 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"4 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8ea7b612b32456ae90fc81c8cfc79b53.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=166467&mlfb=3RB3113-4TE0"},"ai":{"faq":[{"question":"What does the 'for message tripped' note on the 3RB3113-4TE0 mean?","answer":"The note indicates the auxiliary contact set (terminals 97/98) is used to signal a tripped condition back to the control system. The signaling contact has its own shock rating — 9g / 11 ms in the tripped position versus 15g / 11 ms for the main contacts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RB3113-4TE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RB3113-4TE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}