{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RG9002-0DE00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RG9002-0DE00","canonicalUrl":"https://aoctrl.com/siemens/3RG9002-0DE00","factsUrl":"https://aoctrl.com/api/mcp/products/3RG9002-0DE00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens AS-Interface F90 module, 16 digital inputs, 20-30 V DC, IP20, 35 mm DIN rail mounting.","salesMarkdown":"## 16-input AS-Interface slave for control-cabinet mounting The Siemens 3RG9002-0DE00 is an AS-Interface F90 module providing 16 digital inputs arranged in four groups of four, each with a dedicated group signal for the voltage supply of the inputs. The input groups are activated individually by the control system setting the respective group signal, and the switching states of the assigned inputs are then read in. An external auxiliary supply of 20 to 30 V DC is required for the output circuits, complying with VDE 0106 (PELV), protection class III.","metaTitle":"Siemens 3RG9002-0DE00 AS-Interface F90 Module, 16 Inputs","metaDescription":"Siemens 3RG9002-0DE00 AS-Interface F90 module with 16 digital inputs, 20-30 V DC, IP20. EOL hot — sourced to order against RFQ. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"D0":"group signal G1 (D0) inputs I 1.1 to I 1.4 (D0 to D3)","D1":"group signal G2 (D1) inputs I 2.1 to I 2.4 (D0 to D3)","D2":"group signal G3 (D2) inputs I 3.1 to I 3.4 (D0 to D3)","D3":"group signal G4 (D3) inputs I 4.1 to I 4.4 (D0 to D3)","Uin":"20 ... 30V","Type":"16 inputs","Depth":"37mm","Width":"90mm","Height":"75mm","Note 1":"The module has four input groups. Each input group has four inputs and a group signal for the voltage supply of the inputs.","Note 2":"The input groups are activated individually by setting of the respective group signal by the control system. The switching states of the assigned inputs are then read in.","Note 3":"An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III.","Iin min":"3mA","Watchdog":"built-in","ID/ID2 code":"F/F","Input Voltage":"20 ... 30V","Input circuit":"PNP transistor","During Storage":"-40 ... +85°C","Function blocks":"required","display of I/Os":"yellow LEDs","lifecycle_stage":"eol_hot","During Operation":"-25 ... +70°C","Fastening Method":"35 mm standard rail mounting","I/O configuration":"7","Connection Sensors":"mechanical contacts","protection class IP":"IP20","Design Of The Product":"F90 module - I/O modules for operation in the control cabinet, IP20","For Signal <1> Minimum":"3mA","Design Of The Slave Type":"standard slave","Number Of Digital Inputs":"16","switching level High min":"20V","Number Of Digital Outputs":"0","Type Of Connection Technology":"PNP transistor","sensor supply using AS-Interface":"short-circuit and overload resistant","display of AS-Interface/diagnostics":"green LED","AS interface total current input max":"70mA","Group signal Output voltage Uout max":"30V","Group signal Output voltage Uout min":"20V","Type Of Voltage Of The Input Voltages":"DC","Type Of Voltage Supply For Power Supply":"using AS-Interface","Property Of The Output Short-Circuit Proof":"No","Group signal current carrying capacity Iout max":"25mA","Type Of Electrical Connection Of The Inputs And Outputs":"screw-type terminals","operating voltage according to AS-Interface spezification":"26.5 ... 31.6V","Property Of The Sensor Supply Short-Circuit And Overload Resistant":"Yes","ampacity of the sensor supply for all inputs at ambient temperature 40 °C":"200mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8327fe9ad46d163b1b117cf4a1b836d9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=352261&mlfb=3RG9002-0DE00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RG9002-0DE00/alternatives.json"},"ai":{"faq":[{"question":"Is 3RG9002-0DE00 compatible with Siemens S7-300?","answer":"The module is an AS-Interface slave (standard slave type) and communicates over the AS-Interface bus, not the S7-300 backplane. It can be used with any AS-Interface master, including those integrated into S7-300 systems via an AS-Interface master module. The ID/ID2 code is F/F."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RG9002-0DE00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RG9002-0DE00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}