{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RG9004-0DB00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RG9004-0DB00","canonicalUrl":"https://aoctrl.com/siemens/3RG9004-0DB00","factsUrl":"https://aoctrl.com/api/mcp/products/3RG9004-0DB00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RG9004-0DB00, AS-Interface F90 module, 4 inputs / 4 outputs, 4A total output current, 35 mm DIN-rail mount, IP20, end-of-life.","salesMarkdown":"## DIN-rail I/O slice with external aux power The 3RG9004-0DB00: It requires an external auxiliary supply of 20 to 30 V DC (PELV, protection class III) to power the output circuits — the AS-Interface cable alone does not carry enough current for the 4 A total output current. ## End-of-life — source while available This module is classified end-of-life (EOL). Availability is limited to existing stock and surplus channels. Confirm your BOM quantity and request a quote — pricing and lead time are confirmed at the time of the RFQ. ## 4 inputs, 4 outputs, 4 A total The four PNP inputs sink 5 mA minimum at signal <1> and draw under 1.5 mA at signal <0>, with a high-level threshold of 10 V minimum. The four solid-state outputs share a total current capacity of 4 A, with built-in short-circuit and induction protection. The module draws up to 270 mA from the AS-Interface bus for its own logic and sensor supply — the external 24 V DC supply handles the output load. ## Addressing and diagnostics Addressing is done via the integrated addressing socket using a standard AS-Interface handheld programmer. The ID/ID2 code is set to 0/F. I/O status is shown by yellow LEDs; AS-Interface communication and diagnostics are indicated by a green/red dual LED. A built-in watchdog monitors the bus communication.","metaTitle":"Siemens 3RG9004-0DB00 AS-Interface Module, 4 I/O, EOL","metaDescription":"Siemens 3RG9004-0DB00 AS-Interface module with 4 inputs / 4 outputs, 4A total output current, IP20, DIN-rail mount. End-of-life — sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"37 mm","Width":"90 mm","Height":"75 mm","Mounting":"35 mm standard rail mounting","IP Rating":"IP20","Product Type":"4 inputs / 4 outputs","Product Status":"End of Life"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f1d18188e22b16c329b0b6b70a6a6e33.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=276576&mlfb=3RG9004-0DB00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RG9004-0DB00/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RG9004-0DB00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RG9004-0DB00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}