{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RG9004-0DB00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RG9004-0DB00","canonicalUrl":"https://aoctrl.com/siemens/3RG9004-0DB00","factsUrl":"https://aoctrl.com/api/mcp/products/3RG9004-0DB00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RG9004-0DB00, AS-Interface F90 module, 4 inputs / 4 outputs, 4A total output current, 35 mm DIN-rail mount, IP20, end-of-life.","salesMarkdown":"## DIN-rail I/O slice with external aux power The 3RG9004-0DB00: It requires an external auxiliary supply of 20 to 30 V DC (PELV, protection class III) to power the output circuits — the AS-Interface cable alone does not carry enough current for the 4 A total output current. ## End-of-life — source while available This module is classified end-of-life (EOL). Availability is limited to existing stock and surplus channels. Confirm your BOM quantity and request a quote — pricing and lead time are confirmed at the time of the RFQ. ## 4 inputs, 4 outputs, 4 A total The four PNP inputs sink 5 mA minimum at signal <1> and draw under 1.5 mA at signal <0>, with a high-level threshold of 10 V minimum. The four solid-state outputs share a total current capacity of 4 A, with built-in short-circuit and induction protection. The module draws up to 270 mA from the AS-Interface bus for its own logic and sensor supply — the external 24 V DC supply handles the output load. ## Addressing and diagnostics Addressing is done via the integrated addressing socket using a standard AS-Interface handheld programmer. The ID/ID2 code is set to 0/F. I/O status is shown by yellow LEDs; AS-Interface communication and diagnostics are indicated by a green/red dual LED. A built-in watchdog monitors the bus communication.","metaTitle":"Siemens 3RG9004-0DB00 AS-Interface Module, 4 I/O, EOL","metaDescription":"Siemens 3RG9004-0DB00 AS-Interface module with 4 inputs / 4 outputs, 4A total output current, IP20, DIN-rail mount. End-of-life — sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Digital Output Modules"],"specifications":{"D0":"IN1/OUT1","D1":"IN2/OUT2","D2":"IN3/OUT3","D3":"IN4/OUT4","Type":"4 inputs / 4 outputs","Depth":"37mm","Width":"90mm","title":"3RG9004-0DB00","Height":"75mm","Note 1":"An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III.","Watchdog":"built-in","Addressing":"possible using integrated addressing socket","ID/ID2 code":"0/F","description":"AS-Interface module F90, digital 4 DI/4 DQ, IP20 4 x inputs for 3-wire sensor 4 x output, 1 A, 24 V DC maximal 6 A for all outputs Connection via Combicon Width 90 mm Combicon connector set 3RX9810-0AA00 must be ordered.","Input circuit":"PNP transistor","During Storage":"-40 ... +85°C","display of I/Os":"yellow LEDs","lifecycle_stage":"eol_hot","During Operation":"-25 ... +70°C","Fastening Method":"35 mm standard rail mounting","I/O configuration":"7","Connection Sensors":"2- and 3-conductor technology","protection class IP":"IP20","Induction Protection":"built-in","Design Of The Product":"F90 module - I/O modules for operation in the control cabinet, IP20","For Signal <1> Minimum":"5mA","Short-Ciruit Protection":"built-in","With Signal <0> Maximum":"1.5mA","Design Of The Slave Type":"standard slave","Number Of Digital Inputs":"4","Type Of Switching Output":"solid state","switching level High min":"10V","Number Of Digital Outputs":"4","Type Of Connection Technology":"2- and 3-conductor PNP transistor","sensor supply using AS-Interface":"short-circuit and overload resistant","Type Of Voltage Of Output Voltages":"DC","display of AS-Interface/diagnostics":"green/red dual LED","AS interface total current input max":"270mA","Outputs total current of all outputs":"4A","Outputs external power supply 24 V DC":"using Combicon plug connector","Type Of Voltage Of The Input Voltages":"DC","Type Of Voltage Supply For Power Supply":"using AS-Interface","Property Of The Output Short-Circuit Proof":"Yes","Type Of Electrical Connection Of The Inputs And Outputs":"combicon connection","operating voltage according to AS-Interface spezification":"26.5 ... 31.6V","Output Current At Digital Output For Signal <1> Rated Value":"1A","Property Of The Sensor Supply Short-Circuit And Overload Resistant":"Yes","ampacity of the sensor supply for all inputs at ambient temperature 40 °C":"200mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f1d18188e22b16c329b0b6b70a6a6e33.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=276576&mlfb=3RG9004-0DB00"},"ai":{"faq":[{"question":"Does 3RG9004-0DB00 require an external auxiliary power supply?","answer":"Yes. The 3RG9004-0DB00 requires an external 20 to 30 V DC auxiliary supply (PELV, protection class III) to power the output circuits. The AS-Interface bus alone supplies only the module logic and sensor power."},{"question":"How to set the address on a 3RG9004-0DB00 AS-Interface module?","answer":"Addressing is performed using a standard AS-Interface handheld programmer connected to the integrated addressing socket on the module. The ID/ID2 code is factory-set to 0/F."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RG9004-0DB00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RG9004-0DB00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}