{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RG9004-0DE00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RG9004-0DE00","canonicalUrl":"https://aoctrl.com/siemens/3RG9004-0DE00","factsUrl":"https://aoctrl.com/api/mcp/products/3RG9004-0DE00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RG9004-0DE00, AS-Interface standard slave, 16 digital inputs in four individually gated groups, PNP transistor inputs, 20–30 VDC, IP20, 35 mm DIN rail mount.","salesMarkdown":"## Input architecture and group gating The 3RG9004-0DE00 is a 16-input digital module for AS-Interface networks, but the inputs are not read continuously. They are arranged in four groups of four (G1 through G4, mapped to D0–D3), and each group is activated individually by the control system setting its group signal before the switching states of the assigned inputs are read in. This gated architecture means the module draws only 70 mA max from the AS-Interface bus, but it also imposes a sequencing requirement in the PLC program — the group signals must be strobed in the correct order to capture all 16 inputs within the bus cycle. ## Power supply and wiring constraints The module requires an external auxiliary supply (AUX POWER) of 20 to 30 V DC, compliant with VDE 0106 (PELV), protection class III, to power the output circuits. The sensor supply itself comes from the AS-Interface cable and is short-circuit and overload resistant. Input circuits use PNP transistors with a minimum switching level of 20 V and a minimum input current of 3 mA. The module accepts mechanical contacts as sensors. IP20 rated, it is intended for control-cabinet installation only — not for washdown or outdoor deployment.","metaTitle":"Siemens 3RG9004-0DE00 AS-Interface 16 Input Module, EOL","metaDescription":"Siemens 3RG9004-0DE00 AS-Interface digital input module, 16 PNP inputs in 4 groups, 20-30 VDC, IP20, DIN rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"D0":"group signal G1 (D0) inputs I 1.1 to I 1.4 (D0 to D3)","D1":"group signal G2 (D1) inputs I 2.1 to I 2.4 (D0 to D3)","D2":"group signal G3 (D2) inputs I 3.1 to I 3.4 (D0 to D3)","D3":"group signal G4 (D3) inputs I 4.1 to I 4.4 (D0 to D3)","Uin":"20 ... 30V","Type":"16 inputs","Depth":"37mm","Width":"90mm","title":"3RG9004-0DE00","Height":"75mm","Note 1":"The module has four input groups. Each input group has four inputs and a group signal for the voltage supply of the inputs.","Note 2":"The input groups are activated individually by setting of the respective group signal by the control system. The switching states of the assigned inputs are then read in.","Note 3":"An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III.","Iin min":"3mA","Watchdog":"built-in","ID/ID2 code":"F/F","description":"AS-Interface module F90, digital 16 DI (multiplexing) 16 x inputs for 2-wire sensor Connection via Combicon Width 90 mm Combicon connector set 3RX9810-0AA00 must be ordered separately","Input Voltage":"20 ... 30V","Input circuit":"PNP transistor","During Storage":"-40 ... +85°C","Function blocks":"required","display of I/Os":"yellow LEDs","lifecycle_stage":"eol_hot","During Operation":"-25 ... +70°C","Fastening Method":"35 mm standard rail mounting","I/O configuration":"7","Connection Sensors":"mechanical contacts","protection class IP":"IP20","Design Of The Product":"F90 module - I/O modules for operation in the control cabinet, IP20","For Signal <1> Minimum":"3mA","Design Of The Slave Type":"standard slave","Number Of Digital Inputs":"16","switching level High min":"20V","Number Of Digital Outputs":"0","Type Of Connection Technology":"PNP transistor","sensor supply using AS-Interface":"short-circuit and overload resistant","display of AS-Interface/diagnostics":"green LED","AS interface total current input max":"70mA","Group signal Output voltage Uout max":"30V","Group signal Output voltage Uout min":"20V","Type Of Voltage Of The Input Voltages":"DC","Type Of Voltage Supply For Power Supply":"using AS-Interface","Property Of The Output Short-Circuit Proof":"No","Group signal current carrying capacity Iout max":"25mA","Type Of Electrical Connection Of The Inputs And Outputs":"combicon connection","operating voltage according to AS-Interface spezification":"26.5 ... 31.6V","Property Of The Sensor Supply Short-Circuit And Overload Resistant":"Yes","ampacity of the sensor supply for all inputs at ambient temperature 40 °C":"200mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$318.90","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cd68f00b5e268db11b01cb645c004312.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=513905&mlfb=3RG9004-0DE00"},"ai":{"faq":[{"question":"Where can I buy Siemens 3RG9004-0DE00?","answer":"Submit a quote request for current availability and pricing — no stock-holding claim is made on this listing."},{"question":"How do I wire and configure the input groups on 3RG9004-0DE00?","answer":"Each of the four input groups (G1 through G4, corresponding to D0 through D3) has four inputs and a group signal for the voltage supply. The control system must activate each group signal individually before reading the switching states of the assigned inputs. An external 20–30 V DC PELV supply is required for the output circuits; the sensor supply comes from the AS-Interface cable."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RG9004-0DE00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RG9004-0DE00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}