{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RH1122-1AP00-0TK1-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RH1122-1AP00-0TK1-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RH1122-1AP00-0TK1-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RH1122-1AP00-0TK1-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS auxiliary contactor, Size S00, order code 3RH1122-1AP00-0TK1-ZX95, 45 mm width, screw and snap-on mounting, 10 A AC-12 operating current at 24 V.","salesMarkdown":"It carries 2 instantaneous contacts (NO/NC configurable) and is rated for 10 A operating current in AC-12 duty at 24 V, which covers resistive and solid-state loads typical of PLC and relay logic outputs. The 10 A AC-12 rating at 24 V is the headline number for control-circuit fit; at 230 V AC-12 it's still good for 6 A, enough for most contactor coil and indicator lamp circuits. Width is 45 mm, depth 72 mm, height 57.5 mm — standard S00 footprint that clips onto a DIN rail (snap-on) or accepts screws for panel mounting. Front protection is IP20 — fine inside a cabinet, not for washdown. Solid conductor terminations accept 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², or 2x 4 mm², which covers most control wiring gauges without pigtails.","metaTitle":"Siemens 3RH1122-1AP00-0TK1-ZX95 SIRIUS Auxiliary Contactor,","metaDescription":"Siemens 3RH1122-1AP00-0TK1-ZX95 SIRIUS auxiliary contactor, Size S00, 45 mm wide, screw/snap-on mount, 10 A AC-12 at 24 V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"0 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting","During Storage":"-55 ... +80 °C","Leading Contact":"0","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-25 ... +60 °C","During Transport":"-55 ... +80 °C","Shock resistance":"10g / 5 ms and 5g / 10 ms","Delayed Switching":"0","Lagging Switching":"0","Mounting position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"Auxiliary contactor","at 24 V rated value":"10 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.27 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"2 A","at 60 Hz rated value":"230 V","at 690 V rated value":"1 A","Instantaneous Contact":"2","For Auxiliary Contacts":"0","Make-Before-Break Switching":"0","Operating current at AC-12 maximum":"10 A","Surge voltage resistance rated value":"6 kV","Reference code acc. to DIN EN 61346-2":"K","Reference code acc. to DIN EN 81346-2":"K","with low demand rate acc. to SN 31920":"40 %","With Degree Of Pollution 3 Rated Value":"690 V","with high demand rate acc. to SN 31920":"75 %","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","Apparent holding power of magnet coil at AC":"4.6 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Of Auxiliary Contacts Instantaneous Contact":"0","Number of NC contacts for auxiliary contacts":"2","Number of NO contacts for auxiliary contacts":"2","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Identification number and letter for switching elements":"22 E","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=282569&mlfb=3RH1122-1AP00-0TK1-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RH1122-1AP00-0TK1-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RH1122-1AP00-0TK1-ZX95?","answer":"The depth is 72 mm, which is standard for the S00 frame size and fits most DIN-rail enclosures without protruding past the gland plate."},{"question":"What conductor sizes does the 3RH1122-1AP00-0TK1-ZX95 accept?","answer":"Solid conductors: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², or 2x 4 mm². That covers typical control wiring from signal-level up to 4 mm² power feeds."},{"question":"Will 3RH1122-1AP00-0TK1-ZX95 drop into a panel specified around 3RT1017-1AP01?","answer":"Both are Size S00 with the same 45 mm width and DIN-rail clip, so the mechanical footprint is identical. The 3RH1122 is an auxiliary contactor (control-circuit switching), while the 3RT1017 is a power contactor (motor-load switching) — they share the same mounting but serve different circuit duties. No rewiring of the DIN rail or enclosure cutout is needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RH1122-1AP00-0TK1-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RH1122-1AP00-0TK1-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}