{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RH1122-2AP00-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RH1122-2AP00-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3RH1122-2AP00-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RH1122-2AP00-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS auxiliary contactor, Size S00, 2 N/O, 45 mm width, 73 mm depth, screw and snap-on mounting, IP20 front protection.","salesMarkdown":"## Switching capacity and contact reliability Rated for 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V AC, this contactor handles pilot-duty and signal-level loads across common control voltages. Operating temperature range -25 to +60 °C, storage down to -55 °C, and shock resistance of 10g / 5 ms (and 5g / 10 ms) suit it for panels on vibrating machinery or in unconditioned enclosures.","metaTitle":"Siemens SIRIUS 3RH1122-2AP00-1AA0 Auxiliary Contactor, Size","metaDescription":"Siemens SIRIUS 3RH1122-2AP00-1AA0 auxiliary contactor, Size S00, 2 N/O, 10 A at 24 V, IP20, screw/snap-on mounting. Current lifecycle stage: active. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Leading Contact":"0","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","Shock Resistance":"10g / 5 ms and 5g / 10 ms","Delayed Switching":"0","Lagging Switching":"0","Mounting Position":"standing, on horizontal mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Contact Reliability":"one incorrect switching operation of 100 million switching operations (17 V, 1 mA)","Degree Of Pollution":"3","Product Designation":"Auxiliary contactor","at 24 V rated value":"10 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.27 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"2 A","at 60 Hz rated value":"230 V","at 690 V rated value":"1 A","Instantaneous Contact":"2","For Auxiliary Contacts":"0","Make-Before-Break Switching":"0","Substance Prohibitance (Date)":"07/01/2006","protection class IP on the front":"IP20","Product Extension Auxiliary Switch":"Yes","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","reference code according to IEC 81346-2":"K","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Touch Protection Against Electrical Shock":"finger-safe","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Of Auxiliary Contacts Instantaneous Contact":"0","apparent holding power of magnet coil at AC":"4.6 VA","apparent pick-up power of magnet coil at AC":"27 VA","with high demand rate according to SN 31920":"75 %","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC","Inductive Power Factor With Closing Power Of The Coil":"0.8","Identification Number And Letter For Switching Elements":"22 E","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Type Of Electrical Connection For Auxiliary And Control Circuit":"Cage Clamp terminals","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000","Design Of The Fuse Link For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=459260&mlfb=3RH1122-2AP00-1AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RH1122-2AP00-1AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RH1122-2AP00-1AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — the part is sourced through independent distribution and quoted to order."},{"question":"Will 3RH1122-2AP00-1AA0 drop into a panel that was specified around 3RH2122-2AV00 without rewiring?","answer":"Both are Size S00 auxiliary contactors with screw/snap-on mounting and the same 45 mm width, so the mechanical footprint is identical. The 3RH1122-2AP00-1AA0 carries 2 N/O contacts; the 3RH2122-2AV00 carries a different contact arrangement (2 N/O + 2 N/C). Check your circuit's contact complement before swapping — if you need the N/C pair, this part alone won't cover it."},{"question":"What compliance documentation does this brand provide for 3RH1122-2AP00-1AA0 (RoHS, REACH, UL, IEC)?","answer":"The part carries a substance prohibitance date of 07/01/2006 (RoHS-relevant). As a Siemens SIRIUS product, it is designed to meet IEC/EN 60947 standards. For specific UL listing or REACH declaration, request the manufacturer's compliance documentation at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RH1122-2AP00-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RH1122-2AP00-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}