{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RH1122-2KF40-0LA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RH1122-2KF40-0LA0","canonicalUrl":"https://aoctrl.com/siemens/3RH1122-2KF40-0LA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RH1122-2KF40-0LA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS auxiliary contactor, size S00, 3RH1122-2KF40-0LA0, 110 V DC coil with integrated varistor, 2 NO + 2 NC contacts, screw and snap-on mounting, IP20 front, depth 123 mm.","salesMarkdown":"It carries 2 normally-open and 2 normally-closed instantaneous contacts, rated for switching at 110 V DC with a coil that draws 11 W on closing and 4 W holding. The 45 mm width and 123 mm depth fit standard S00 panel layouts. Terminal capacity accepts 0.25 to 2.5 mm² solid or stranded wire — 2 conductors per clamp. Contact reliability is rated at one incorrect switching operation per 100 million cycles at 17 V, 1 mA — suitable for low-energy PLC or sensor signals. The AC-15 / DC-13 switching capacity varies by voltage: at 24 V the contacts switch 10 A, at 110 V they switch 1 A, at 230 V they switch 6 A, and at 400 V they switch 3 A. These ratings govern the actual load the contacts can break under inductive or resistive conditions. Shock resistance is 10g for 5 ms and 5g for 10 ms. RoHS compliance date is July 1, 2006 — the part meets the original RoHS directive.","metaTitle":"Siemens 3RH1122-2KF40-0LA0 SIRIUS Auxiliary Contactor, 110 V","metaDescription":"Siemens SIRIUS 3RH1122-2KF40-0LA0 auxiliary contactor, size S00, 110 V DC coil with varistor, 2 NO + 2 NC contacts, IP20 front, current lifecycle stage. Available to order, quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"123 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Rated Value":"110 V","Initial Value":"0.7","During Storage":"-55 ... +80 °C","Leading Contact":"0","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","Full-Scale Value":"1.25","Shock Resistance":"10g / 5 ms and 5g / 10 ms","Delayed Switching":"0","Lagging Switching":"0","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Contact Reliability":"one incorrect switching operation of 100 million switching operations (17 V, 1 mA)","Degree Of Pollution":"3","Product Designation":"Auxiliary contactor","at 24 V rated value":"10 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.27 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"2 A","at 690 V rated value":"1 A","Instantaneous Contact":"2","For Auxiliary Contacts":"0","Make-Before-Break Switching":"0","Substance Prohibitance (Date)":"07/01/2006","Design Of The Surge Suppressor":"with varistor","protection class IP on the front":"IP20","Product Extension Auxiliary Switch":"Yes","closing power of magnet coil at DC":"11 W","holding power of magnet coil at DC":"4 W","Surge Voltage Resistance Rated Value":"6 kV","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (24 ... 14)","reference code according to IEC 81346-2":"K","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Touch Protection Against Electrical Shock":"finger-safe","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Of Auxiliary Contacts Instantaneous Contact":"0","with high demand rate according to SN 31920":"75 %","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"DC","Identification Number And Letter For Switching Elements":"21 E","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Type Of Electrical Connection For Auxiliary And Control Circuit":"Cage Clamp terminals","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000","Design Of The Fuse Link For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/73fa68dd7222060f124ee51cd2b2bbc0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=84071&mlfb=3RH1122-2KF40-0LA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RH1122-2KF40-0LA0/alternatives.json"},"ai":{"faq":[{"question":"What is the coil voltage for 3RH1122-2KF40-0LA0?","answer":"The coil is rated at 110 V DC, with an integrated varistor for surge suppression. Closing power draw is 11 W, holding power is 4 W."},{"question":"Where can I buy 3RH1122-2KF40-0LA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the contact ratings for this auxiliary contactor?","answer":"The contacts are rated 10 A at 24 V, 1 A at 110 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. Contact reliability is one incorrect operation per 100 million cycles at 17 V, 1 mA."},{"question":"Does 3RH1122-2KF40-0LA0 have the same footprint as 3RH2122-1BW40?","answer":"Both are S00 size auxiliary contactors with similar DIN-rail mounting, so they share the same 45 mm width and general panel footprint. However, verify coil voltage and contact configuration — the 3RH2122-1BW40 may differ in coil rating or contact arrangement. No direct drop-in guarantee without checking those specifics."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RH1122-2KF40-0LA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RH1122-2KF40-0LA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}