{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RH1326-1XH00-0AB2","brand":"Siemens","brandSlug":"siemens","productSlug":"3RH1326-1XH00-0AB2","canonicalUrl":"https://aoctrl.com/siemens/3RH1326-1XH00-0AB2","factsUrl":"https://aoctrl.com/api/mcp/products/3RH1326-1XH00-0AB2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS auxiliary contactor, size S00, 4 NO + 2 NC, 45 mm width, screw and snap-on mounting, IP20 front.","salesMarkdown":"## Part identity and fit It is designed for control-circuit switching in motor starter assemblies and general panel logic — it extends the contact count of a main contactor or acts as an interposing relay. The contacts are rated 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. These are thermal (AC-1) currents for resistive loads; for inductive or motor-duty circuits, derate per the AC-15 or DC-13 curves the SIRIUS manual provides. The 6 kV surge voltage resistance means the contactor withstands transient overvoltages common in industrial control panels without flashover — important when switching coils or solenoids on the same bus. The IP20 front protection is standard for enclosed panel gear; it prevents finger contact but is not rated for washdown environments. This flexibility simplifies panel layout when space is tight. It handles 10g / 5 ms and 5g / 10 ms shock — sufficient for machine-mounted applications near presses or conveyors. The screw terminals accept solid conductors: 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², and 2x 4 mm². This covers standard control wiring from signal-level pairs up to power-feed runs for auxiliary circuits.","metaTitle":"Siemens SIRIUS 3RH1326-1XH00-0AB2 Auxiliary Contactor, 4 NO","metaDescription":"Siemens SIRIUS 3RH1326-1XH00-0AB2 auxiliary contactor, size S00, 4 NO + 2 NC contacts, rated 10 A at 24 V, IP20 front. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"111 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.88 ... 1.1","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Leading Contact":"0","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","Shock Resistance":"10g / 5 ms and 5g / 10 ms","Delayed Switching":"0","Lagging Switching":"0","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Contact Reliability":"one incorrect switching operation of 100 million switching operations (17 V, 1 mA)","Degree Of Pollution":"3","Product Designation":"Auxiliary contactor","at 24 V rated value":"10 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.27 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"48 V","at 500 V rated value":"2 A","at 60 Hz rated value":"48 V","at 690 V rated value":"1 A","Instantaneous Contact":"2","For Auxiliary Contacts":"0","Make-Before-Break Switching":"0","Substance Prohibitance (Date)":"07/01/2006","protection class IP on the front":"IP20","Product Extension Auxiliary Switch":"No","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","reference code according to IEC 81346-2":"K","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Touch Protection Against Electrical Shock":"finger-safe","with low demand rate according to SN 31920":"40 %","Of Auxiliary Contacts Instantaneous Contact":"0","apparent holding power of magnet coil at AC":"4.6 VA","apparent pick-up power of magnet coil at AC":"27 VA","with high demand rate according to SN 31920":"75 %","number of NC contacts for auxiliary contacts":"6","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC","Inductive Power Factor With Closing Power Of The Coil":"0.8","Identification Number And Letter For Switching Elements":"26","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Type Of Electrical Connection For Auxiliary And Control Circuit":"screw-type terminals","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Design Of The Fuse Link For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=312797&mlfb=3RH1326-1XH00-0AB2","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RH1326-1XH00-0AB2/alternatives.json"},"ai":{"faq":[{"question":"What are the key contact ratings for this auxiliary contactor?","answer":"The contacts are rated 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V for resistive loads. For inductive or motor-duty circuits, derate per the AC-15 or DC-13 curves."},{"question":"What is the mounting method and panel footprint?","answer":"It uses screw and snap-on mounting for DIN rail. The width is 45 mm, height 57.5 mm, and depth 111 mm. It fits the same footprint as SIRIUS 3RT1 contactors."},{"question":"What compliance documentation is available for this part?","answer":"The part is RoHS compliant with a substance prohibition date of July 1, 2006. It carries a 6 kV surge voltage resistance rating and IP20 front protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RH1326-1XH00-0AB2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RH1326-1XH00-0AB2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}