{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RH1344-2CP00-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RH1344-2CP00-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3RH1344-2CP00-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RH1344-2CP00-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS auxiliary contactor, 3RH1344-2CP00-0KA0, size S00, 4 NO instantaneous contacts, screw and snap-on mounting, 45 mm width.","salesMarkdown":"It provides four normally open (NO) instantaneous contacts and is rated for a mechanical endurance of 10,000,000 operating cycles. The contactor's rated operational current varies with voltage and frequency: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V. At 50 Hz the rated operational current range is 0.8 to 1.1 A; at 60 Hz it is 0.85 to 1.1 A. These values define the continuous current the contacts can carry and interrupt under normal conditions — a 10 A rating at 24 V covers most PLC output and relay coil loads, while the 1 A at 690 V accommodates higher-voltage control circuits in 690 V line-fed panels. The 45 mm wide, 60 mm tall, 114 mm deep footprint fits the standard S00 contactor slot on a DIN rail. Fastening is by screw and snap-on mounting. ## Environmental and surge protection Shock resistance is 10 g / 5 ms and 5 g / 10 ms, which covers most industrial vibration environments short of direct hammer-mill mounting. The built-in surge suppressor uses a varistor, so no external RC snubber is needed for coil suppression on AC control circuits — a detail that saves panel space and wiring time.","metaTitle":"Siemens 3RH1344-2CP00-0KA0 SIRIUS Auxiliary Contactor, 4 NO","metaDescription":"Siemens SIRIUS auxiliary contactor 3RH1344-2CP00-0KA0, 4 NO contacts, size S00, 45mm wide. Screw and snap-on mounting. Rated 10A at 24V.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Leading Contact":"0","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","Shock Resistance":"10g / 5 ms and 5g / 10 ms","Delayed Switching":"0","Lagging Switching":"0","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Contact Reliability":"one incorrect switching operation of 100 million switching operations (17 V, 1 mA)","Degree Of Pollution":"3","Product Designation":"Auxiliary contactor","at 24 V rated value":"10 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.27 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"2 A","at 60 Hz rated value":"230 V","at 690 V rated value":"1 A","Instantaneous Contact":"4","For Auxiliary Contacts":"0","Make-Before-Break Switching":"0","Substance Prohibitance (Date)":"07/01/2006","Design Of The Surge Suppressor":"with varistor","protection class IP on the front":"IP20","Product Extension Auxiliary Switch":"No","Surge Voltage Resistance Rated Value":"6 kV","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (24 ... 14)","reference code according to IEC 81346-2":"K","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Touch Protection Against Electrical Shock":"finger-safe","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Of Auxiliary Contacts Instantaneous Contact":"0","apparent holding power of magnet coil at AC":"4.6 VA","apparent pick-up power of magnet coil at AC":"27 VA","with high demand rate according to SN 31920":"75 %","number of NC contacts for auxiliary contacts":"4","number of NO contacts for auxiliary contacts":"4","Type Of Voltage Of The Control Supply Voltage":"AC","Inductive Power Factor With Closing Power Of The Coil":"0.8","Identification Number And Letter For Switching Elements":"44","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Type Of Electrical Connection For Auxiliary And Control Circuit":"Cage Clamp terminals","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Design Of The Fuse Link For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=317967&mlfb=3RH1344-2CP00-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RH1344-2CP00-0KA0/alternatives.json"},"ai":{"faq":[{"question":"Is 3RH1344-2CP00-0KA0 compatible with the 3RH2 series?","answer":"The 3RH1344-2CP00-0KA0 belongs to the SIRIUS 3RH1 family (size S00). Compatibility with the 3RH2 series depends on the specific mounting rail and contact configuration — verify the footprint and terminal layout against your existing panel cutout before specifying."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RH1344-2CP00-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RH1344-2CP00-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}