{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RH1362-2BB40","brand":"Siemens","brandSlug":"siemens","productSlug":"3RH1362-2BB40","canonicalUrl":"https://aoctrl.com/siemens/3RH1362-2BB40","factsUrl":"https://aoctrl.com/api/mcp/products/3RH1362-2BB40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS auxiliary contactor, 3RH1362-2BB40, 24 V DC coil, 6 NO instantaneous contacts, size S00, screw and snap-on mounting, IP20 front.","salesMarkdown":"The coil pulls 3.2 W DC and holds at the same power, which means the supply transformer or DC bus needs to budget that draw continuously while the contactor is energized. The front is IP20-rated, so it's protected against accidental finger contact but not against washdown — keep it inside the cabinet. The 6 NO contacts are rated for AC and DC switching across common control voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. That covers most 24 VDC PLC outputs and 230 VAC pilot-duty circuits in a single device. The contacts are instantaneous (no make-before-break or delayed action), so they switch cleanly with the coil state. The surge voltage withstand is 6 kV, adequate for industrial environments with moderate transient exposure. This part is a standard catalog item from the Siemens SIRIUS line. It carries a substance prohibition date of 01.07.2006, aligning with RoHS compliance for lead and other restricted substances. No UL or CSA mark is listed in the evidence, but the IEC ratings cover most global installations outside North America — verify local code acceptance if the panel requires a UL-listed auxiliary contactor.","metaTitle":"Siemens 3RH1362-2BB40 SIRIUS Auxiliary Contactor, 24 V DC, 6","metaDescription":"Siemens SIRIUS 3RH1362-2BB40 auxiliary contactor, 24 V DC coil, 6 instantaneous NO contacts, size S00, screw/snap-on mounting, IP20. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Rated Value":"24 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Leading Contact":"0","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"screw and snap-on mounting","Full-Scale Value":"1.1","Shock Resistance":"10g / 5 ms and 5g / 10 ms","Delayed Switching":"0","Lagging Switching":"0","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Contact Reliability":"one incorrect switching operation of 100 million switching operations (17 V, 1 mA)","Degree Of Pollution":"3","Product Designation":"Auxiliary contactor","at 24 V rated value":"10 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.27 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"2 A","at 690 V rated value":"1 A","Instantaneous Contact":"6","For Auxiliary Contacts":"0","Make-Before-Break Switching":"0","Substance Prohibitance (Date)":"01.07.2006 00:00:00","protection class IP on the front":"IP20","Product Extension Auxiliary Switch":"No","closing power of magnet coil at DC":"3.2 W","holding power of magnet coil at DC":"3.2 W","reference code acc. to IEC 81346-2":"K","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","with low demand rate acc. to SN 31920":"40 %","with high demand rate acc. to SN 31920":"75 %","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Touch Protection Against Electrical Shock":"finger-safe","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Of Auxiliary Contacts Instantaneous Contact":"0","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"6","Type Of Voltage Of The Control Supply Voltage":"DC","B10 value with high demand rate acc. to SN 31920":"1 000 000; With 0.3 x Ie","Identification Number And Letter For Switching Elements":"62 E","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Type Of Electrical Connection For Auxiliary And Control Circuit":"Cage Clamp terminals","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Design Of The Fuse Link For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$41.96","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=462418&mlfb=3RH1362-2BB40","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RH1362-2BB40/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of the 3RH1362-2BB40?","answer":"The contactor is 45 mm wide, 60 mm tall, and 114 mm deep — size S00 footprint."},{"question":"What is the coil voltage and power consumption?","answer":"The coil is rated 24 V DC and draws 3.2 W closing and holding."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RH1362-2BB40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RH1362-2BB40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}