{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK1300-0AS10-1AA4","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK1300-0AS10-1AA4","canonicalUrl":"https://aoctrl.com/siemens/3RK1300-0AS10-1AA4","factsUrl":"https://aoctrl.com/api/mcp/products/3RK1300-0AS10-1AA4","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RK1300-0AS10-1AA4, electronic reversing starter, solid-state motor protection, setting range 0.6...2.18A, AC-3 0.18...0.75kW/400V, IP65, PROFIBUS DP, with brake contact.","salesMarkdown":"The Siemens 3RK1300-0AS10-1AA4 is an electronic reversing starter from the SIRIUS family, designed for ET 200X distributed I/O environments. The setting range covers 0.6 to 2.18 A, corresponding to motor ratings of 0.18 to 0.8 kW at AC-3 duty on a 400 V supply. The solid-state switching contacts mean no mechanical wear on the main poles, and the integrated motor protection eliminates the need for a separate overload relay — the unit handles both reversing and overload protection in one package. The AC-3 rating of 0.8 kW at 400 V defines the maximum induction motor load this starter can handle under normal starting and stopping conditions. That covers small conveyors, pumps, and fan drives up to about 1 HP. The minimum setting of 0.18 kW means it can also protect fractional-horsepower motors down to 0.25 HP, which is useful for small feed drives or agitators. This is a coordination value — the upstream fuse must be selected per the manufacturer's guidelines to ensure the solid-state output is not damaged during a short circuit. Operating voltage range 400 to 500 V AC. DC control voltage means brake output and logic supply require a DC source. The IP65 protection class means the housing is dust-tight and protected against water jets from any direction. This allows mounting in washdown areas or outdoors without a separate cabinet, as long as the cable glands and connectors are also rated for the environment. ## Integration and connectivity PROFIBUS DP communication is built in (product function bus communication: Yes), so the starter can exchange status, diagnostics, and control commands directly with a PLC over the fieldbus without a separate gateway. This is the main differentiator from a conventional reversing contactor — you get remote monitoring of motor current, thermal state, and fault codes. The main current circuit connects via tab terminals, which are common on distributed I/O modules like ET 200X. The unit includes a motor brake output (product component motor brake output: Yes) rated DC 500 V / 1 A, allowing direct control of a holding brake on vertical-axis drives without an external relay. Ambient temperature range during operation is 0 to 55 °C. If mounted in a non-ventilated enclosure near other heat sources, derate the continuous current or add forced ventilation to stay within the thermal limits of the solid-state output stage.","metaTitle":"Siemens 3RK1300-0AS10-1AA4 Electronic Reversing Starter, 0.6","metaDescription":"Siemens SIRIUS 3RK1300-0AS10-1AA4 electronic reversing starter, solid-state motor protection, 0.6-2.18A setting range, 0.18-0.8kW at AC-3 400V, IP65, PROFIBUS DP, brake contact. Cu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Remote I/O & Fieldbus Modules"],"specifications":{"Depth":"134mm","Width":"140mm","Height":"270mm","Maximum":"0.8kW","Minimum":"0.18kW","Initial Value":"0.6A","Type of voltage":"DC","lifecycle_stage":"current","Full-scale value":"2.18A","Protection class IP":"IP65","PROFIBUS DP protocol":"Yes","AS-interface protocol":"No","Design of the product":"reversing starter","Type of the motor protection":"solid-state","at AC-3 at 400 V rated value":"0.8kW","Operating voltage rated value":"400 ... 500V","Design of the switching contact":"solid-state","Design of short-circuit protection":"fuse","Product function Bus communication":"Yes","Ambient temperature during operation":"0 ... 55°C","Product component Motor brake output":"Yes","Equipment marking acc. to DIN EN 61346-2":"Q","Type of electrical connection for main current circuit":"tab terminals","Maximum short-circuit current breaking capacity (Icu) at 400 V rated value":"100A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=15296&mlfb=3RK1300-0AS10-1AA4","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK1300-0AS10-1AA4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK1300-0AS10-1AA4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK1300-0AS10-1AA4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}