{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK1301-0FB00-0AA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK1301-0FB00-0AA2","canonicalUrl":"https://aoctrl.com/siemens/3RK1301-0FB00-0AA2","factsUrl":"https://aoctrl.com/api/mcp/products/3RK1301-0FB00-0AA2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC motor starter, direct starter, 3RK1301-0FB00-0AA2, 24 V DC, CLASS 10, 50 kA at 400 V, PROFINET/PROFIBUS DP.","salesMarkdown":"## SIMATIC direct starter — 3RK1301-0FB00-0AA2 The Siemens 3RK1301-0FB00-0AA2 is a SIMATIC direct starter motor starter, designed for direct-on-line starting of three-phase motors. The unit is pluggable on a terminal module, so it swaps without disturbing the power wiring. Rated 50 kA at 400 V — that is the short-circuit breaking capacity at the main incoming supply level. For a panel fed from a 400 V transformer with an SCCR requirement above 50 kA, this starter coordinates cleanly without needing upstream fuses to clip the fault current. The 24 V DC control supply (20.4 to 28.8 V range) is standard for modern PLC cabinets; the unit pulls its logic power from the same 24 V bus as the rest of the SIMATIC I/O. Operating frequency is rated at a maximum of 750 1/h — that is about one start every 4.8 seconds. Fine for most conveyor and fan duty; not suited for high-cycle indexing or rapid reversing (reverse starting is explicitly not supported). Mounting is vertical or horizontal, and the 45 mm width and 120 mm depth fit standard 45 mm DIN-rail spacing. ## Network integration — PROFINET and PROFIBUS DP This starter supports both PROFINET and PROFIBUS DP protocols natively. The digital I/O map is 1 byte input and 1 byte output — enough for start/stop feedback, fault status, and a few diagnostic bits. No additional gateway or communication module is needed; it connects directly to the PLC via the network cable. Shock resistance is 5 g for 11 ms, vibration resistance 2 g — suitable for panel mounting in industrial environments with moderate vibration. Degree of pollution is 3 at 400 V and 2 at 500 V per IEC 60664, which covers most factory floor conditions (conductive dust, occasional condensation).","metaTitle":"Siemens 3RK1301-0FB00-0AA2 SIMATIC Motor Starter, CLASS 10,","metaDescription":"Siemens 3RK1301-0FB00-0AA2 SIMATIC motor starter, direct start, CLASS 10, 50 kA at 400 V, 24 V DC, PROFINET/PROFIBUS DP. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"120 mm","Width":"45 mm","Height":"265 mm","Mounting":"pluggable on terminal module","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$411.48","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f364642fd5f31cab1654dcf6dd146b4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=162336&mlfb=3RK1301-0FB00-0AA2","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK1301-0FB00-0AA2/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK1301-0FB00-0AA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK1301-0FB00-0AA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}