{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK1315-6LS41-2AA5","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK1315-6LS41-2AA5","canonicalUrl":"https://aoctrl.com/siemens/3RK1315-6LS41-2AA5","factsUrl":"https://aoctrl.com/api/mcp/products/3RK1315-6LS41-2AA5","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RK1315-6LS41-2AA5 direct motor starter, AS-Interface, 5.5 kW at 400 V, IP65, Class 10, 4 digital inputs, 159 x 294 x 215 mm.","salesMarkdown":"## SIRIUS direct starter with AS-Interface — what it is and where it fits The 3RK1315-6LS41-2AA5 is a Siemens SIRIUS direct starter — a self-contained motor start-and-protect unit that combines a contactor, overload relay, and AS-Interface communication in one IP65 enclosure. It is designed for distributed motor control where the starter sits near the motor rather than in a central panel, saving cabinet space and reducing point-to-point wiring. Rated 5.5 kW at 400 V (7.5 hp at 460/480 V, 10 hp at 575/600 V), it covers the common small-motor range for pumps, fans, conveyors, and small compressors in industrial and infrastructure installations. ## Supply voltage, motor power, and trip coordination The control supply is 24 VDC nominal, with a permissible range of 20.4 to 28.8 V DC — the 26.5 V minimum permissible and 31.6 V maximum permissible define the absolute limits for the internal electronics. A 24 VDC supply with ±15 % regulation keeps the unit inside its operating window. Motor power ratings are given per voltage region: 5.5 kW at 400 V, 5 500 W at 500 V (same value, different notation), 3 hp at 220/230 V, 7.5 hp at 460/480 V, and 10 hp at 575/600 V. The Trip Class is CLASS 10, meaning the overload relay trips within 10 seconds at 7.2× the set current — standard for general-purpose motor protection where the starting time is short. ON-delay time is 85 ms, OFF-delay time is 65 ms — these are the internal response times from the AS-Interface command to the power contacts changing state. For sequencing multiple starters, account for these delays in the PLC logic if coordinated start/stop timing matters. ## Mounting, enclosure, and environmental fit The unit measures 159 mm deep, 294 mm wide, and 215 mm high, with screw fixing as the fastening method. Mounting can be vertical, horizontal, or flat — the recommended orientation is horizontal, which aligns with the natural convection path for the overload relay's thermal memory. IP65 protection means the enclosure is dust-tight and protected against low-pressure water jets — suitable for washdown areas, outdoor cabinets, and locations where the starter is mounted directly on the machine frame rather than in a sealed panel. Pollution degree 3 confirms it is rated for conductive pollution typical of industrial floors. Operating temperature range is -25 to +55 °C, with storage and transport limits of -40 to +70 °C. Shock resistance is 12g for 11 ms, and vibration resistance is 7 mm at 2g — adequate for mounting on machinery with moderate vibration, though a direct-coupled pump or fan on a rigid base is the typical fit. ## I/O, fieldbus, and connectivity The starter communicates via AS-Interface protocol — no PROFIBUS DP or PROFINET on this variant. AS-Interface is a bit-level fieldbus suited for simple on/off control and status feedback from distributed devices; it carries the start/stop command and returns the overload trip signal and motor current data. Four digital inputs are integrated into the unit, allowing local pushbuttons or sensors to be wired directly without a separate I/O block. Device addressing is via an M12 plug, and the main current circuit connects through a HAN Q4/2 connector per ISO 23570 — a standard industrial rectangular connector for motor power. On-site operation is supported — meaning the starter can be manually operated via a local button or selector switch for commissioning and maintenance, independent of the fieldbus command.","metaTitle":"Siemens 3RK1315-6LS41-2AA5 SIRIUS Motor Starter","metaDescription":"Siemens 3RK1315-6LS41-2AA5 SIRIUS direct starter, 5.5 kW at 400 V, IP65, AS-Interface, Class 10. Active production — quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"NRND","categoryPath":[],"specifications":{"Depth":"159 mm","Width":"294 mm","Height":"215 mm","Mounting":"screw fixing","IP Rating":"IP65","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f33c49a23e5dc03b85cecc58e372928.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=524801&mlfb=3RK1315-6LS41-2AA5","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK1315-6LS41-2AA5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK1315-6LS41-2AA5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK1315-6LS41-2AA5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}