{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK1395-6KS71-3AD5-Z E09","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK1395-6KS71-3AD5-Z-E09","canonicalUrl":"https://aoctrl.com/siemens/3RK1395-6KS71-3AD5-Z-E09","factsUrl":"https://aoctrl.com/api/mcp/products/3RK1395-6KS71-3AD5-Z%20E09","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS M200D Technology Module, reversing starter, electronic switching AC-3, 0.75 kW / 400 V, 0.15…2.00 A, electronic overload protection, thermistor, brake contact 180 V DC, 4 DI / 2 DO, Han Q4/2 - Han Q8/0, manual on-site operation, key-operated switch, for PROFIBUS or PROFINET via communication module 3RK1305*.","salesMarkdown":"The Siemens 3RK1395-6KS71-3AD5-Z E09 is a SIRIUS M200D Technology Module configured as a reversing motor starter — electronic switching in AC-3 duty, rated 0.15 to 2.00 A and 0.75 kW at 400 V. The integrated thermistor (THERMOCLICK / PTC) input gives direct motor temperature feedback, so you catch a winding overheat before the overload curve alone would. A brake contact rated at 180 V DC is included, which saves an external contactor on applications with spring-set brakes — conveyors, gantries, vertical axes. The module carries 4 digital inputs and 2 digital outputs, and connects via Han Q4/2 and Han Q8/0 connectors. It communicates on PROFIBUS or PROFINET through a separate communication module (3RK1305*). Manual on-site operation with a key-operated switch is built in, so you can jog or isolate the starter locally during commissioning without reaching for a laptop. That matters when you're on a ladder at 2 AM trying to index a turntable. ## What the ratings mean in practice The 0.15 to 2.00 A current range covers small reversing applications — think 0.37 kW to 0.75 kW motors at 400 V three-phase. The electronic overload is adjustable across that range, so one module fits multiple motor sizes on the same line, which simplifies spares stocking. The brake contact at 180 V DC handles most spring-set brakes on small servo and induction motors; verify your brake coil voltage matches before wiring. The four digital inputs and two digital outputs give you local feedback and control without pulling extra I/O from the PLC. Typical use: two inputs for forward/reverse commands, one for a limit switch, one for a fault reset; outputs can drive a status lamp or a brake release confirmation. The Han connectors (Q4/2 and Q8/0) are a mixed power/signal interface — you'll need the matching cable sets for a clean panel build. The Han connectors mean pre-fabricated cables are available, which speeds up panel wiring versus terminal-by-terminal termination. Manual on-site operation with a key switch is a commissioning time-saver: you can test direction and brake release without the PLC online.","metaTitle":"Siemens 3RK1395-6KS71-3AD5-Z E09 M200D Reversing Starter, NR","metaDescription":"Siemens SIRIUS M200D reversing motor starter, 0.15-2.00 A, AC-3 0.75 kW at 400V, electronic overload, 4DI/2DO, brake contact 180V DC. NRND — sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"NRND","categoryPath":["Remote I/O & Fieldbus Modules"],"specifications":{"Group Code":"R711","Product Group":"3722","Product class":"A: Standard product which is a stock item could be returned within the returns guidelines/period.","Quantity Unit":"1 Piece","Product Family":"Ordering Data Overview","lifecycle_stage":"current","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : 9N9999","Packaging dimensions (L x W x H)":"377.00 x 287.00 x 221.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 01-07-06","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1f1d7ebe9c298e5cee67267182e8c4f.pdf","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/3RK1395-6KS71-3AD5-ZE09?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK1395-6KS71-3AD5-Z%20E09/alternatives.json"},"ai":{"faq":[{"question":"What is the listed group code and product group for this part?","answer":"The Group Code is R711 and the Product Group is 3722. These are Siemens internal classification codes used for catalog sorting and cross-referencing within the SIRIUS portfolio."},{"question":"What compliance documentation is available for this motor starter?","answer":"RoHS compliance is confirmed since July 1, 2006. REACH Article 33 notification applies due to lead content (CAS 7439-92-1) above 0.1% w/w. No UL or IEC certification marks are listed in the available documentation."},{"question":"How do I source this part given the NRND status?","answer":"We source the 3RK1395-6KS71-3AD5-Z E09 to order against an RFQ. Submit a request with your quantity and target delivery window, and we will confirm availability from the channel. For new BOM lines, Siemens recommends evaluating the current-generation M200D or M300D starters."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK1395-6KS71-3AD5-Z-E09","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK1395-6KS71-3AD5-Z-E09 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}