{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK2100-1CT30-0AA3","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK2100-1CT30-0AA3","canonicalUrl":"https://aoctrl.com/siemens/3RK2100-1CT30-0AA3","factsUrl":"https://aoctrl.com/api/mcp/products/3RK2100-1CT30-0AA3","rawCanonicalId":null},"summary":{"shortDescription":"Siemens AS-Interface K20 digital output module, 3RK2100-1CT30-0AA3, 4 PNP outputs, 2 A max, IP67, for field I/O.","salesMarkdown":"## AS-i Field Output Module, 4-Channel The Siemens 3RK2100-1CT30-0AA3 is a K20 digital output module for AS-Interface networks, delivering 4 PNP transistor outputs rated at 2 A total at 40 °C. It requires an external 20–30 V DC auxiliary power supply (PELV per VDE 0106, protection class III) to drive the output circuits — the AS-i bus cable alone cannot supply the load current. The module is a full A/B slave compliant with AS-i Specification 3.0, with an ID/ID2 code of A/7 and an I/O configuration of 7. Built for direct field mounting, the IP67 housing (108 × 45 × 20 mm) needs no backplate and accepts M12 connectors for both the AS-i bus and the external AUX supply. Four M12 sockets each map pin 4 to one output (OUT1–OUT4), with pin 3 wired to the common negative. Integrated short-circuit protection, induction suppression, and a watchdog are standard — no external clamp diodes or fuses needed per channel. This order code is in its current lifecycle stage — still active in the Siemens AS-Interface portfolio. ## Integration Notes Operates from –25 to +70 °C, stores from –40 to +85 °C, and withstands 15 g shock at 11 ms — rugged enough for conveyor-adjacent or washdown-zone mounting. The AS-i bus draws 45 mA from the master; the output load current comes entirely from the external 24 V DC AUX feed, so plan a separate PELV supply in the panel. Yellow LEDs per output and a green LED for AUX power give quick status at the module face; the dual red/green AS-i LED reports bus communication and diagnostics. No mounting plate is required — the module clips directly to a machine frame or bracket.","metaTitle":"Siemens 3RK2100-1CT30-0AA3 AS-i K20 Module, 4 Outputs, 2 A,","metaDescription":"Siemens 3RK2100-1CT30-0AA3 AS-Interface K20 digital output module, 4 PNP outputs, max 2 A at 40 °C, IP67, requires external 24 V DC AUX supply. Current lifecycle stage.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"45 mm","Width":"20 mm","Height":"108 mm","Mounting":"no mounting plate required","IP Rating":"IP67","Product Type":"4 outputs","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/94f5f0762c731242fa945b088ac546ef.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=175132&mlfb=3RK2100-1CT30-0AA3","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK2100-1CT30-0AA3/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK2100-1CT30-0AA3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK2100-1CT30-0AA3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}