{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK3511-1BA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK3511-1BA10","canonicalUrl":"https://aoctrl.com/siemens/3RK3511-1BA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RK3511-1BA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, interface module DP interface, for modular safety system 3RK3, PROFIBUS DP 12 Mbps, RS-485, 45 mm width, screw terminal, IP20, NRND.","salesMarkdown":"## PROFIBUS DP gateway for the 3RK3 safety system The Siemens 3RK3511-1BA10 is a SIRIUS DP-interface module that bridges the modular safety system 3RK3 to a PROFIBUS DP network at up to 12 Mbps over RS-485. It is the communication gateway for parameterizing the safety logic via Safety ES software — no separate connection cable needed. The module snaps onto a DIN rail in a vertical position and occupies 45 mm of panel width, with a 111 mm height and 124 mm depth. Power is 24 V DC, and the inrush current hits 70 A for 1 ms at startup — brief but enough to trip a marginal supply if you don't account for it. The IP20 enclosure means it lives inside a cabinet, not on the machine frame. Shock rated to 15g / 11 ms and vibration tested per IEC 60068-2-6 (0.75 mm at 5–500 Hz), so it holds up on a panel door or subplate near rotating equipment. Manufacturer status is NRND (Not Recommended for New Designs). Siemens supports existing installations. For new projects, use the current-generation gateway. The module is RoHS-compliant per the substance prohibition date of 05/01/2012. It carries a reference code per IEC 81346-2 (K) and is designed for pollution degree 2 environments — typical for clean, dry control cabinets. ## Wiring and integration notes Screw terminals accept solid conductors up to 1x 4 mm² or 2x 2.5 mm², and finely stranded with ferrule up to 1x 2.5 mm² or 2x 1.5 mm². AWG equivalents for auxiliary contacts are 2x 20–14. Installation altitude is limited to 2,000 m above sea level without derating. Operating humidity range is 10–95% relative. The burst immunity per IEC 61000-4-4 is 2 kV on power ports, which is standard for industrial control panels.","metaTitle":"Siemens 3RK3511-1BA10 SIRIUS DP Interface, NRND","metaDescription":"Siemens 3RK3511-1BA10 SIRIUS interface module for modular safety system 3RK3. PROFIBUS DP at 12 Mbps, 45 mm wide, IP20, NRND. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"NRND","categoryPath":[],"specifications":{"Depth":"124 mm","Width":"45 mm","Height":"111 mm","Mounting":"DIN Rail","IP Rating":"IP20","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/60f5df92fbaebdba8919393acd1b28d5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=349979&mlfb=3RK3511-1BA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK3511-1BA10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK3511-1BA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK3511-1BA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}