{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RK4320-3ER51-1BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RK4320-3ER51-1BA0","canonicalUrl":"https://aoctrl.com/siemens/3RK4320-3ER51-1BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RK4320-3ER51-1BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RK4320-3ER51-1BA0 reversing motor starter, 1.6 A AC-3 at 400 V, Class 10, IP55, AS-Interface communication, 145 x 182 x 220 mm.","salesMarkdown":"## Mounting and enclosure fit The 3RK4320-3ER51-1BA0: The unit measures 145 mm deep, 182 mm wide, and 220 mm high — a compact footprint for a reversing starter with integrated bus communication. It mounts on a vertical surface with ±180° rotation possible and can be tilted forward or backward by ±22.5°, giving panel builders flexibility in tight enclosures. ## Supply and control voltages The main circuit operates at 340-440 V AC, 50/60 Hz. The control supply is 20.4-26.4 V DC — a standard 24 V DC nominal rail with ±10% tolerance. The AS-Interface protocol is supported natively, so no external gateway module is needed for AS-i bus integration.","metaTitle":"Siemens 3RK4320-3ER51-1BA0 SIRIUS Reversing Starter, 1.6 A","metaDescription":"Siemens SIRIUS 3RK4320-3ER51-1BA0 reversing motor starter, 1.6 A at AC-3 400 V, Class 10, IP55, AS-Interface. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Depth":"145 mm","Width":"182 mm","Height":"220 mm","Trip Class":"CLASS 10","Type Of Voltage":"DC","lifecycle_stage":"current","Bus Communication":"Yes","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","PROFINET protocol":"No","Product Brand Name":"SIRIUS","Type Of Assignment":"1","Product Designation":"motor starter MCU for AS-Interface","protection class IP":"IP55","PROFIBUS DP protocol":"No","Design Of The Product":"reversing starter","Number Of Digital Inputs":"0","Short Circuit Protection":"Yes","at AC at 400 V rated value":"1.6 A","brake control with 24 V DC":"No","Operating Frequency Minimum":"80 1/h","brake control with 180 V DC":"No","brake control with 400 V AC":"No","brake control with 500 V DC":"No","Type Of The Motor Protection":"bimetal","at AC-3 at 400 V rated value":"1.6 A","Operating Voltage Rated Value":"340 ... 440 V","Substance Prohibitance (Date)":"05/01/2012","Design Of The Switching Contact":"electromechanical","Operating Frequency 1 Rated Value":"50 Hz","Operating Frequency 2 Rated Value":"60 Hz","Design Of Short-Circuit Protection":"circuit-breakers","Ambient Temperature During Operation":"-25 ... +35 °C","Product Component Motor Brake Output":"No","Type Of Voltage Of The Supply Voltage":"DC","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","control supply voltage at DC rated value":"20.4 ... 26.4 V","with low demand rate according to SN 31920":"50 %","protocol is supported AS-Interface protocol":"Yes","with high demand rate according to SN 31920":"75 %","operating power at AC-3 at 400 V rated value":"0.6 kW","Product Extension Braking Module For Brake Control":"No","Relative Negative Tolerance Of The Operating Frequency":"-10 %","Relative Positive Tolerance Of The Operating Frequency":"10 %","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","breaking capacity maximum short-circuit current (Icu) at 400 V rated value":"50 000 A","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d5a35fc9511ddebc2ff9d15d3c7fdd1b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=366864&mlfb=3RK4320-3ER51-1BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RK4320-3ER51-1BA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3RK4320-3ER51-1BA0?","answer":"Submit an RFQ through this listing."},{"question":"What is the AC-3 motor rating at 400 V?","answer":"The AC-3 rated current at 400 V is 1.6 A. This is the switching current for motor loads — the value that determines whether the starter can handle your motor's full-load amps during start and run."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RK4320-3ER51-1BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RK4320-3ER51-1BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}