{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RN1013-2BB00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RN1013-2BB00","canonicalUrl":"https://aoctrl.com/siemens/3RN1013-2BB00","factsUrl":"https://aoctrl.com/api/mcp/products/3RN1013-2BB00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RN1013-2BB00 thermistor motor protection evaluation unit, 24 V AC/DC, 2 CO contacts, spring-loaded terminals, IP20, 22.5 mm width.","salesMarkdown":"The Siemens 3RN1013-2BB00 is a thermistor motor protection evaluation unit from the SIRIUS family. It monitors PTC thermistor sensors embedded in motor windings and trips the control circuit when the winding temperature exceeds the sensor's rated response threshold — preventing a burn-out before the overload relay alone would act. The unit accepts a 24 V control supply regardless of whether the panel runs AC or DC — the Type Of Voltage is AC/DC, with rated values of 24 V at 50 Hz, 60 Hz, and DC. That simplifies stocking for mixed-supply sites. It provides two changeover (CO) contacts for auxiliary signaling — one typically wired to the motor contactor coil, the other to a PLC input or alarm annunciator. There are no dedicated NO or NC contacts; the two COs give flexibility to configure the fail-safe state. ## Mounting and wiring in the panel Housing is 22.5 mm wide, 103 mm tall, 91 mm deep — a standard single-module footprint that clips onto a DIN rail (screw and snap-on mounting). The 22.5 mm width keeps the panel density high; you can fit several evaluation units side by side without crowding the gland plate. An LED on the front confirms the operating status (display version LED: Yes). That helps a field tech quickly see if the unit is powered and whether it has tripped, without needing a meter. ## Environmental limits and compliance The storage range is wider, but the operating limit governs the panel's ambient design. The part carries a RoHS compliance date of May 28, 2009, indicating it meets the EU RoHS directive for substances. No UL or CSA mark is stated in the evidence; check the specific nameplate or request certification documents if your site requires them. ## Sourcing reality — phased out with a defined successor For existing BOM lines or installed bases, the 3RN1013-2BB00 can still be sourced through independent channels on a quoted-to-order basis. No last-time-buy date is published; the successor is the recommended path for new designs.","metaTitle":"Siemens 3RN1013-2BB00 Thermistor Motor Protection, 24 V AC/D","metaDescription":"Siemens 3RN1013-2BB00 thermistor motor protection evaluation unit. 24 V AC/DC control, 2 CO contacts, IP20, spring terminals. Phased out; successor 3RN2013-2BA30 available. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Process / Temperature Controllers"],"specifications":{"Depth":"91 mm","Width":"22.5 mm","Height":"103 mm","Type Of Voltage":"AC/DC","lifecycle_stage":"current","Fastening Method":"screw and snap-on mounting","at DC rated value":"24 V","display version LED":"Yes","protection class IP":"IP20","at 50 Hz rated value":"24 V","at 60 Hz rated value":"24 V","Substance Prohibitance (Date)":"05/28/2009","Product Function Reclosing Lockout":"Yes","Ambient Temperature During Operation":"-25 ... +60 °C","reference code according to IEC 81346-2":"K","number of CO contacts for auxiliary contacts":"2","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","1 For Auxiliary And Control Circuit Rated Value":"50 Hz","2 For Auxiliary And Control Circuit Rated Value":"60 Hz","Type Of Electrical Connection For Auxiliary And Control Circuit":"spring-loaded terminals"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/3RN1013-2BB00/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 3RN1013-2BB00?","answer":"It operates on 24 V AC/DC control supply, provides 2 CO contacts, fits a 22.5 mm DIN-rail footprint, and is rated IP20 with spring-loaded terminals. Ambient temperature range is -25 °C to +60 °C."},{"question":"How do I source the 3RN1013-2BB00?","answer":"As a phased-out part, it is available through independent distributors on a quoted-to-order basis. Submit an RFQ for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RN1013-2BB00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RN1013-2BB00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}