{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AB01-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AB01-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AB01-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AB01-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S00 power contactor, 3RT1015-1AB01-ZW96, screw-type terminals, 24 V 50/60 Hz coil, 10 A auxiliary contact, 3 kW at 400 V AC-3, 4 kW at 690 V AC-3.","salesMarkdown":"It carries a 24 V 50/60 Hz coil, an instantaneous auxiliary contact rated 10 A at 24 V, and delivers 3 kW at 400 V AC-3 or 4 kW at 690 V AC-3. The screw-type terminals accept 2x (0.5 to 4 mm²) conductors, and the contactor mounts via screw or snap-on onto 35 mm DIN rail per EN 50022. The S00 frame size (45 mm wide, 57.5 mm high, 72 mm deep) is the smallest SIRIUS contactor footprint — it fits tight DIN-rail layouts where panel space is at a premium. The 10 A auxiliary contact at 24 V covers PLC-level signal switching; the 2 A rating at 60 V and 0.3 A at 220 V show it can handle pilot-duty loads across common control voltages. Motor power ratings of 3 kW at 400 V AC-3 and 4 kW at 690 V AC-3 define the maximum three-phase induction motor it can switch under normal starting duty. For AC-4 (plugging/reversing) at 400 V, the current limit drops to 6.5 A — a key derating factor if the application involves frequent inching or reversing. Short-circuit coordination is specified: with type 2 coordination (limited damage to contactor after fault), use a gL/gG fuse rated 20 A; with type 1 coordination (contactor may need replacement), use 35 A. This matters for selectivity studies and fuse sizing in the feeder circuit. The 3RT1015-1AB01-ZW96 is a general-purpose power contactor for switching three-phase motors up to 4 kW in conveyors, pumps, fans, compressors, and small machine tools. It also switches resistive loads (AC-1) up to 10 A, making it suitable for heater banks and lighting contactor panels. The IP20 finger-safe terminals on the front and at the connection side mean it can be installed in open control panels without additional shrouding.","metaTitle":"Siemens 3RT1015-1AB01-ZW96 SIRIUS S00 Contactor, 10A Aux, 3k","metaDescription":"Siemens 3RT1015-1AB01-ZW96 SIRIUS power contactor, size S00, screw terminals, 24 V 50/60 Hz coil, 10 A auxiliary contact, 3 kW at 400 V / 4 kW at 690 V. Active production. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"24 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"24 V","at 690 V rated value":"4 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=230850&mlfb=3RT1015-1AB01-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AB01-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor power ratings for the 3RT1015-1AB01-ZW96?","answer":"It is rated 3 kW at 400 V AC-3 and 4 kW at 690 V AC-3 for three-phase induction motor switching. For AC-4 duty (reversing/plugging) at 400 V, the current limit is 6.5 A."},{"question":"What is the coil voltage and frequency for this contactor?","answer":"The coil is rated 24 V at both 50 Hz and 60 Hz, with an operating range of 0.8 to 1.1 times rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz."},{"question":"What wire sizes does the screw terminal accept?","answer":"The main circuit screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."},{"question":"Will the 3RT1015-1AB01-ZW96 drop into a panel designed for the 3RT1016-2AP02?","answer":"Both are S00 frame size contactors with the same 45 mm width and DIN-rail mounting, so the physical footprint and rail position are identical. The difference is in coil voltage and auxiliary contact configuration — verify the control circuit voltage and aux contact count match your panel wiring before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AB01-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AB01-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}