{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AB02-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AB02-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AB02-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AB02-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 24 VAC coil 50/60 Hz, screw-type terminals, 45 mm wide, DIN-rail mount.","salesMarkdown":"## SIRIUS Size S00 power contactor — 24 VAC coil, screw terminals The 24 VAC coil (rated at 50/60 Hz) pulls in across 0.8 to 1.1 times rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz, so it holds in through typical line sags without drop-out. Screw-type terminals on the main circuit accept up to 2x 4 mm² stranded or 1x 12 AWG, matching the wiring common on 4 kW (690 V) or 3.5 kW (500 V) motor circuits. ## Motor duty and coordination — AC-2, AC-4, and short-circuit ratings For short-circuit coordination, Type 2 (no damage to the contactor or starter) requires a 20 A gL/gG fuse; Type 1 (contactor may need replacement) allows a 35 A fuse. That 20 A limit tells you the panel designer should size the upstream protection for selectivity with downstream motor loads, not just the contactor's thermal rating. ## Auxiliary contact ratings and wiring The contactor carries a built-in auxiliary contact block rated for 10 A at 24 V (AC-12 resistive), 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC. The auxiliary wiring accepts the same screw-terminal range as the main circuit: 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², or max 2x 0.75 to 4 mm² solid/stranded.","metaTitle":"Siemens 3RT1015-1AB02-ZX95 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT1015-1AB02-ZX95 power contactor, Size S00, 24 VAC coil, 50/60 Hz. Screw terminals, DIN-rail mount. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"24 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"24 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=273287&mlfb=3RT1015-1AB02-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AB02-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1015-1AB02-ZX95 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not a published figure."},{"question":"What is the closest functional second-source to 3RT1015-1AB02-ZX95?","answer":"The 3RT1016-1AG61 is a Size S00 peer with a 24 VDC coil, not 24 VAC. The 3RT1015-1AB02-ZX95 uses a 24 VAC coil; swapping to a DC-coil variant requires verifying the control transformer and rectifier circuit in the panel. The 3RT1016-2AP02 is a larger-frame contactor and will not drop into the same DIN-rail footprint without rewiring."},{"question":"What is 3RT1015-1AB02-ZX95's listed depth?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm — a compact Size S00 footprint that fits standard 35 mm DIN-rail enclosures."},{"question":"What compliance documentation does Siemens provide for 3RT1015-1AB02-ZX95?","answer":"The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC) for this order code. For a BOM freeze or export compliance review, request the manufacturer's declaration from the supplier at quote time."},{"question":"Will 3RT1015-1AB02-ZX95 drop into a panel specified around 3RT1016-1AG61 without rewiring?","answer":"Mechanically yes — both are Size S00 with screw and snap-on mounting onto 35 mm DIN rail. Electrically no: the 3RT1015-1AB02-ZX95 has a 24 VAC coil, while the 3RT1016-1AG61 uses 24 VDC. The control circuit must supply AC; a DC coil on an AC supply will not pull in reliably."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AB02-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AB02-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}