{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AG61","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AG61","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AG61","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AG61","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1015-1AG61, size S00, 24 VDC coil, screw-type terminals, 45 mm width, IP20.","salesMarkdown":"It is rated for a 24 VDC coil, pulling in at 10 A at 24 V rated value, and carries motor power ratings of 3.5 kW at 500 V and 4 kW at 690 V. For AC-2 duty at 400 V it is rated at 3 kW, and for AC-4 duty at 400 V it handles 6.5 A — the AC-4 figure governs reversing or inching applications where the contactor makes and breaks the motor current under load. The 45 mm width and 57.5 mm height fit into a standard DIN-rail enclosure bay; depth is 72 mm, which clears most 80 mm deep enclosures. Terminals are screw-type for both the main current circuit and the auxiliary/control circuit. Accepts solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16) and 2x (18 to 14), with a single 12 AWG allowed. This covers standard panel wiring up to 4 mm² for the power circuit. ## Switching Capacity and Duty Ratings The contactor's switching capacity varies by voltage and duty type. At 24 V rated value it switches 10 A; at 60 V rated value 2 A; at 110 V rated value 1 A; at 220 V rated value 0.3 A; at 230 V rated value 6 A; at 400 V rated value 3 A. These figures cover the resistive and light inductive load range. The coil holds at 24 VDC nominal with an operating range of 0.85 to 1.1 times rated voltage at both 50 Hz and 60 Hz. ## Protection and Environmental Ratings ## Short-Circuit Coordination","metaTitle":"Siemens 3RT1015-1AG61 SIRIUS Power Contactor, S00, 24 VDC 10","metaDescription":"Siemens 3RT1015-1AG61 SIRIUS power contactor, size S00, 24 VDC coil rated 10 A. Active production. Screw terminals, 45 mm wide, IP20. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"100 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"100 ... 110 V","at 690 V rated value":"4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Substance Prohibitance (Date)":"01.07.2006 00:00:00","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","reference code acc. to IEC 81346-2":"Q","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","apparent holding power of magnet coil at AC":"5.1 V·A","apparent pick-up power of magnet coil at AC":"31.7 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","Inductive Power Factor With Closing Power Of The Coil":"0.77","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=282590&mlfb=3RT1015-1AG61","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AG61/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the 3RT1015-1AG61?","answer":"24 VDC coil rated at 10 A. Motor power ratings: 3.5 kW at 500 V and 4 kW at 690 V. AC-4 duty at 400 V is 6.5 A. Frame size S00, 45 mm wide, screw-type terminals."},{"question":"What is the depth of the 3RT1015-1AG61?","answer":"The depth is 72 mm, which fits standard 80 mm deep enclosures."},{"question":"What conductor sizes does the 3RT1015-1AG61 accept?","answer":"Screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded. AWG equivalents: 2x (20 to 16) and 2x (18 to 14), with a single 12 AWG allowed."},{"question":"Does the 3RT1015-1AG61 drop into a panel specified for the 3RT1017-1AP01?","answer":"Both are S00 frame contactors on a 45 mm wide DIN-rail footprint, so the mechanical fit is the same. The difference is in coil voltage and ratings — verify the 24 VDC coil and switching capacity against your BOM before substituting."},{"question":"What compliance documentation is available for the 3RT1015-1AG61?","answer":"The part carries a RoHS compliance date of 01.07.2006. Reference code per IEC 81346-2 is Q. Standard Siemens SIRIUS documentation includes CE, UL, and CSA certifications — consult the product documentation for specific approval marks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AG61","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AG61 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}