{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AH01-ZW95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AH01-ZW95","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AH01-ZW95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AH01-ZW95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1015-1AH01-ZW95 power contactor, size S00, 24 VDC coil, 10 A AC-12, 3 kW AC-2 at 400 V, screw terminals, DIN rail mount.","salesMarkdown":"## SIRIUS 3RT1015-1AH01-ZW95 — Power Contactor, Size S00, 24 VDC Coil The 24 VDC coil draws its rated current at the listed operating range of 0.8 to 1.1 times the rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz — ensure the control supply stays within these bounds for reliable pick-up and drop-out. Rated for AC-12 duty at 10 A maximum, this contactor handles resistive loads up to that current. For motor duty, the AC-2 rating at 400 V is 3 kW, and the AC-4 rating at 400 V is 6.5 A — the AC-4 figure governs reversing or inching applications where the contacts break the motor at full current. ## DIN Rail Integration and Wiring Main circuit terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max. 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. Front and terminal protection is IP20. Dimensions: 45 mm wide, 57.5 mm high, 72 mm deep — fits standard S00 footprint. Pollution degree 3 for industrial environments. For type 1 coordination, the required fuse is gL/gG 35 A; for type 2 coordination, it is gL/gG 20 A.","metaTitle":"Siemens SIRIUS 3RT1015-1AH01-ZW95 Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT1015-1AH01-ZW95 power contactor, size S00, 24 VDC coil, 10 A AC-12, 3 kW AC-2 at 400 V. DIN rail mount, IP20. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"48 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"48 V","at 690 V rated value":"4 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=169643&mlfb=3RT1015-1AH01-ZW95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AH01-ZW95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1015-1AH01-ZW95 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing."},{"question":"What are the key ratings of 3RT1015-1AH01-ZW95?","answer":"Key ratings include: 24 VDC coil, 10 A AC-12 maximum operating current, 3 kW AC-2 at 400 V, 6.5 A AC-4 at 400 V, and 4 kW at 690 V."},{"question":"What is the depth of 3RT1015-1AH01-ZW95?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm, fitting the standard S00 contactor footprint."},{"question":"What wire sizes does 3RT1015-1AH01-ZW95 accept?","answer":"Main circuit terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max. 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."},{"question":"Will 3RT1015-1AH01-ZW95 drop into a panel specified for 3RT1016-1AG61?","answer":"Both are size S00 contactors with the same DIN rail mounting and similar footprint. The 3RT1016-1AG61 has a different coil voltage and ratings; verify the coil voltage and load ratings match your application before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AH01-ZW95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AH01-ZW95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}