{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AL01","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AL01","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AL01","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AL01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1015-1AL01, screw-type terminals, 24 VDC coil, snap-on DIN rail mounting.","salesMarkdown":"The coil is rated at 24 VDC with a pickup range of 0.8 to 1.1 times rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz, meaning it holds in reliably across brownout conditions down to about 19 V. Rated operational current at 24 V is 10 A, and at 400 V AC-4 duty it carries 6.5 A — that's the switching category for reversing or inching motor loads, where the contactor breaks the full motor current at each cycle. The AC-12 maximum operating current is 10 A, covering resistive loads like heaters or lighting banks. The auxiliary contact block is a single instantaneous contact (NO or NC depending on wiring). Main circuit terminals are screw-type, accepting solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. The IP20 finger-safe protection on the front and terminals means it's safe for open-panel mounting where maintenance staff may reach in.","metaTitle":"Siemens 3RT1015-1AL01 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens 3RT1015-1AL01 SIRIUS power contactor, size S00. 24 VDC coil, 10 A rated at 24 V. Screw terminals, snap-on DIN rail mount. Current production. Available to order. Get a quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"125 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"125 V","at 690 V rated value":"4 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=150263&mlfb=3RT1015-1AL01","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AL01/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1015-1AL01 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3RT1015-1AL01?","answer":"The depth is 72 mm, width 45 mm, height 57.5 mm — the S00 frame size fits standard 45 mm-wide DIN rail slots."},{"question":"What compliance documentation does Siemens provide for 3RT1015-1AL01?","answer":"The part carries IP20 protection on front and terminals, pollution degree 3, and is rated for use up to 2000 m altitude. Standard Siemens declarations for RoHS and REACH are available with the product documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AL01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AL01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}