{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AN62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AN62","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AN62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AN62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1015-1AN62, 24 V DC coil, screw-type terminals, 3 kW AC-2 at 400 V, snap-on 35 mm DIN rail.","salesMarkdown":"The 3RT1015-1AN62: The AC-2 rating at 400 V is 3 kW — that is the motor duty for slip-ring rotors or moderate inrush loads, not the higher AC-3 figure you might expect from a larger frame. AC-4 reversing duty at 400 V is 6.5 A, so if the application calls for plugging or inching, that is the current ceiling. For type 2 coordination (no-weld fault protection) the required backup fuse is 20 A gL/gG; type 1 coordination allows 35 A gL/gG. That fuse choice directly affects the SCCR of the branch circuit. Terminals accept 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), or max 2x (0.75…4 mm²) solid/stranded — common for control wiring up to 4 mm². The front face is IP20, so finger-safe once wired; side clearances are 6 mm for adjacent devices. Pollution degree 3 (conductive pollution expected) suits it for factory-floor panels without climate control.","metaTitle":"Siemens 3RT1015-1AN62 SIRIUS Power Contactor, S00 Frame, 3 k","metaDescription":"Siemens SIRIUS 3RT1015-1AN62 power contactor, S00 size, screw terminals, 24 V DC coil, rated 3 kW at 400 V AC-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"200 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"200 ... 220 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=340706&mlfb=3RT1015-1AN62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AN62/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1015-1AN62?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time."},{"question":"What is the difference between 3RT1015-1AN62 and 3RT1016-1AG61?","answer":"The 3RT1016-1AG61 uses an AC coil at 24 V 50/60 Hz, while the 3RT1015-1AN62 uses a 24 V DC coil. Both are S00 frame and share the same footprint and terminal layout, so mechanical swap is possible, but the coil supply must match — DC coil on an AC supply will not hold in, and vice versa."},{"question":"What is the depth of 3RT1015-1AN62?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm — the standard S00 envelope."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AN62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AN62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}