{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AP02-ZW95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AP02-ZW95","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AP02-ZW95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AP02-ZW95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1015-1AP02-ZW95 power contactor, Size S00, 45 mm width, 24 VDC coil, screw terminals, snap-on DIN rail mounting.","salesMarkdown":"It carries a 24 VDC coil and is rated for 10 A at 24 V in AC-12 duty, which is the resistive-load curve for auxiliary or control circuits, not the motor-starting curve. The 45 mm width and snap-on mounting to 35 mm DIN rail (per DIN EN 50022) mean it fits standard panel layouts without extra bracketing. The headline 10 A at 24 V is the AC-12 resistive rating — the current it can make and break for purely resistive loads like heaters or control transformers. For motor duty, the ratings shift: at AC-2 (slip-ring motors) it handles 3 kW at 400 V, and at AC-4 (plugging/inching) it's rated 6.5 A at 400 V. The operating temperature range of -25 to +60 °C covers most indoor panel environments, but the pollution degree 3 rating means it's intended for environments with conductive pollution (condensation, light dust) unless it's enclosed in a higher-rated cabinet. ## Panel integration The 72 mm depth is shallow enough for shallow enclosures, and the 57.5 mm height fits standard DIN-rail spacing. Screw terminals accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, with a maximum of 2x (0.75 to 4 mm²) — that covers most control wiring gauges. The IP20 finger-safe protection on the front and terminals means it's touch-safe in an enclosed panel but not washdown-rated.","metaTitle":"Siemens 3RT1015-1AP02-ZW95 SIRIUS Power Contactor, S00, 24 V","metaDescription":"Siemens 3RT1015-1AP02-ZW95 SIRIUS power contactor, Size S00, 45 mm wide, 24 VDC coil, 10 A rated at 24 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=460728&mlfb=3RT1015-1AP02-ZW95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AP02-ZW95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3RT1015-1AP02-ZW95?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery timeline."},{"question":"What is the closest functional second-source to the 3RT1015-1AP02-ZW95?","answer":"The 3RT1016-1AG61 is a Size S00 contactor with a similar footprint, but it uses a 24 VAC/DC coil and has different terminal arrangements — verify the coil voltage and wiring diagram before substituting. The 3RT1016-2AP02 is a higher-current variant (same frame, higher rating) that may require coordination re-evaluation."},{"question":"What is the depth of the 3RT1015-1AP02-ZW95?","answer":"The depth is 72 mm, which is standard for the S00 frame and fits most shallow enclosures."},{"question":"What wire sizes does the 3RT1015-1AP02-ZW95 accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, and up to 2x (0.75 to 4 mm²) maximum. For AWG, that's 2x (20 to 16) solid, 2x (18 to 14) stranded, and 1x 12 AWG."},{"question":"Will the 3RT1015-1AP02-ZW95 drop into a panel specified for a 3RT1016-1AG61?","answer":"The physical footprint (S00 frame, 45 mm width, DIN rail mounting) is identical, so it will mount in the same rail position. The difference is the coil: the 3RT1015-1AP02-ZW95 uses a 24 VDC coil, while the 3RT1016-1AG61 uses a 24 VAC/DC coil. If your control circuit is pure DC, this is a direct swap; if it's AC, you need to re-verify coil supply."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AP02-ZW95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AP02-ZW95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}