{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1AT62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1AT62","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1AT62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AT62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1015-1AT62 power contactor, size S00, 3 NO main contacts, screw-type terminals, AC-4 rated 6.5 A at 400 V, snap-on 35 mm DIN rail mount.","salesMarkdown":"## Motor switching and auxiliary ratings Auxiliary contact capacity is 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. For DC switching, the contactor handles 2 A at 60 V and 0.3 A at 220 V. ## Short-circuit coordination and wiring The screw terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or a maximum of 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), or 1x 12. The manufacturer provides standard compliance documentation including the EU Declaration of Conformity (CE) and the manufacturer's declaration for the UKCA mark. RoHS and REACH declarations are available on request.","metaTitle":"Siemens 3RT1015-1AT62 SIRIUS Power Contactor, S00, 3 NO, 6.5","metaDescription":"Siemens SIRIUS 3RT1015-1AT62 power contactor, size S00, 3 NO main contacts, 6.5 A AC-4 at 400 V. Current lifecycle stage. Screw terminals, snap-on DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 60 Hz":"0.8 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"600 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=155099&mlfb=3RT1015-1AT62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1AT62/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT1015-1AT62?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution channels."},{"question":"What is the closest functional second-source for 3RT1015-1AT62?","answer":"The 3RT1016-1AG61 is a size S00 contactor from the same SIRIUS family, but it has a different coil voltage (230 V AC) and different auxiliary contact configuration. Verify coil compatibility and auxiliary contact count before substituting into a panel designed for the 3RT1015-1AT62."},{"question":"What is 3RT1015-1AT62's depth?","answer":"The depth is 72 mm."},{"question":"What wire sizes does the screw terminal accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or a maximum of 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), or 1x 12."},{"question":"What compliance documentation is available for 3RT1015-1AT62?","answer":"The manufacturer provides CE and UKCA declarations. RoHS and REACH declarations are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1AT62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1AT62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}