{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-1JB41-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-1JB41-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-1JB41-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1JB41-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, order code 3RT1015-1JB41-ZX95, 24 VDC coil, 10 A at 24 V, screw terminals, DIN rail mount, IP20 front.","salesMarkdown":"It switches 10 A at 24 V (AC-12) and carries motor ratings of 3.5 kW at 500 V and 4 kW at 690 V. The 24 VDC coil draws 2.3 W both on closing and holding — no power penalty for keeping it engaged. The integrated diode suppresses the inductive kickback from the coil, which matters when the contactor shares a DC supply with sensitive electronics like a PLC output card. Without that diode, the flyback voltage can couple noise into the 24 V bus. In AC-4 (reversing or plugging) at 400 V, it handles 6.5 A. The AC-1 resistive rating reaches 20 A at 400 V. These numbers define the real load envelope — the AC-3 figure governs most conveyor and pump starts. Short-circuit coordination is specified: type 2 coordination requires a 20 A gL/gG fuse; type 1 allows up to 35 A gL/gG. If the panel design calls for type 2 to minimize downtime after a fault, the 20 A fuse limit is the binding constraint on upstream protection. Screw terminals accept solid conductors from 0.5 mm² up to 4 mm² (max 2x 4 mm² per clamp).","metaTitle":"Siemens 3RT1015-1JB41-ZX95 SIRIUS Power Contactor, 24 VDC, S","metaDescription":"Siemens 3RT1015-1JB41-ZX95 SIRIUS power contactor, size S00, 24 VDC coil, 10 A at 24 V. DIN rail mount, IP20 front. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.7","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.25","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"3.5 kW","at 690 V rated value":"4 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Design of the surge suppressor":"with diode","Closing power of magnet coil at DC":"2.3 W","Holding power of magnet coil at DC":"2.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"18 A","Type of voltage of the control supply voltage":"DC","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=263515&mlfb=3RT1015-1JB41-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-1JB41-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1015-1JB41-ZX95?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm, fitting the S00 frame footprint."},{"question":"What conductor sizes does the 3RT1015-1JB41-ZX95 accept?","answer":"The screw terminals accept solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-1JB41-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-1JB41-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}