{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-2AB01-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-2AB01-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-2AB01-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AB01-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1015-2AB01-ZX95, size S00, 24 V 50/60 Hz coil, spring-loaded terminals, IP20, screw and snap-on 35 mm DIN rail.","salesMarkdown":"The Siemens SIRIUS 3RT1015-2AB01-ZX95 is a size S00 power contactor with a 24 V 50/60 Hz coil, spring-loaded terminals on both main and auxiliary circuits, and an IP20 finger-safe enclosure. The auxiliary contact block is rated 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — these are the make/break currents the aux contacts can handle in a control circuit, so if your PLC output drives a 24 VDC relay through this contactor's aux, the 10 A rating gives ample headroom. For motor loads, the contactor is rated 3 kW at 400 V in AC-2 duty and 6.5 A at 400 V in AC-4 duty — AC-2 covers slip-ring motor starting, AC-4 covers plugging and inching. Type 2 coordination requires a 20 A gL/gG fuse; Type 1 coordination allows a 35 A gL/gG fuse. That difference matters for selectivity studies — Type 2 leaves the contactor undamaged after a fault, Type 1 may require replacement. Dimensions are 45 mm wide, 60 mm high, 73 mm deep — the S00 frame footprint. Spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded, or 2x (24 to 14 AWG). No screw torque to verify — spring clamp gives consistent contact force regardless of the installer's technique.","metaTitle":"Siemens 3RT1015-2AB01-ZX95 SIRIUS Contactor, S00, 24V 50/60H","metaDescription":"Siemens SIRIUS 3RT1015-2AB01-ZX95 power contactor, size S00, 24V 50/60Hz coil, spring terminals, IP20. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,25 ... 2,5 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"24 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"24 V","at 690 V rated value":"4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Substance Prohibitance (Date)":"01.07.2006 00:00:00","at AWG cables for main contacts":"2x (24 ... 14)","For Auxiliary And Control Circuit":"spring-loaded terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","reference code acc. to IEC 81346-2":"Q","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","apparent holding power of magnet coil at AC":"4.4 V·A","apparent pick-up power of magnet coil at AC":"27 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","Inductive Power Factor With Closing Power Of The Coil":"0.8","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=356415&mlfb=3RT1015-2AB01-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AB01-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1015-2AB01-ZX95 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3RT1015-2AB01-ZX95 drop into a panel specified around 3RT1015-1AG61?","answer":"Both are S00 frame contactors with the same 45 x 60 x 73 mm footprint and 35 mm DIN rail mount, so the mechanical fit is identical. The difference is the coil voltage — this one is 24 V 50/60 Hz, while the 1AG61 uses a different coil. Verify your control voltage before swapping."},{"question":"What compliance documentation does Siemens provide for 3RT1015-2AB01-ZX95?","answer":"The part carries a RoHS substance prohibition date of 01.07.2006, confirming RoHS compliance. Standard Siemens documentation includes the declaration of conformity and CE marking; UL and CSA listings are typical for the SIRIUS series but not confirmed in this specific variant's evidence."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-2AB01-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-2AB01-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}