{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-2AN62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-2AN62","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-2AN62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AN62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1015-2AN62, 10 A at 24 V, spring-loaded terminals, 45 mm wide, IP20 front.","salesMarkdown":"Rated 10 A at 24 V, it also carries 6 A at 230 V and 3 A at 400 V, covering common line voltages. The AC-2 rating at 400 V is 3 kW, and the AC-4 rating at 400 V is 6.5 A — the AC-4 figure is the one that governs reversing or inching duty where the contactor makes and breaks the motor current every cycle. Spring-loaded terminals on the main circuit accept 2x (0.25... 2.5 mm²) solid or stranded wire, or 2x (24... 14 AWG). No screw torque to check — strip to 8 mm, push in, done. The control circuit uses the same terminal type. Pollution degree 3 means it handles conductive dust and condensation typical of industrial panels — no conformal coating required for most environments. The mechanical life is 30,000,000 cycles — this contactor is rated for high-cycle applications like conveyor jogging or valve actuation where the contacts cycle many times per shift. The AC-12 operating current maximum of 10 A is the resistive load limit; stay under that for heater or lighting circuits. Type 1 and Type 2 coordination fusing is specified: a gL/gG 35 A fuse for Type 1 (contactor may be damaged but no fire risk), and a gL/gG 20 A fuse for Type 2 (contactor survives the fault). Use the Type 2 rating if you need to avoid replacing the contactor after a short circuit. No auxiliary contact blocks are integrated — the instantaneous contact count is zero. If you need N.O./N.C. signaling, order a separate side-mount auxiliary switch block from the SIRIUS range.","metaTitle":"Siemens 3RT1015-2AN62 SIRIUS Power Contactor, Size S00, 10 A","metaDescription":"Siemens 3RT1015-2AN62 SIRIUS power contactor, size S00, 10 A at 24 V, spring-loaded terminals, 35 mm DIN rail mount, IP20. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"200 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"200 ... 220 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=239579&mlfb=3RT1015-2AN62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AN62/alternatives.json"},"ai":{"faq":[{"question":"Will 3RT1015-2AN62 drop into a panel that was specified around 3RT1016-2AP02 without rewiring?","answer":"Both are size S00 SIRIUS contactors with the same 45 mm width and DIN rail footprint, so the mechanical fit is identical. The terminal type differs — 3RT1015-2AN62 uses spring-loaded terminals, while the peer uses a different termination. If the panel was wired for screw terminals, you may need to re-terminate the wires."},{"question":"What compliance documentation does this brand provide for 3RT1015-2AN62?","answer":"Siemens SIRIUS contactors carry CE, UL, CSA, and CCC certifications as standard. RoHS and REACH declarations are available from the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-2AN62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-2AN62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}