{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-2AP02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-2AP02","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-2AP02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AP02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, order code 3RT1015-2AP02, 24 VDC coil, spring-loaded terminals, 10 A rated operational current.","salesMarkdown":"The spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, so termination is vibration-resistant and fast to commission. The S00 footprint — 45 mm wide, 60 mm tall, 73 mm deep — fits standard panel layouts and leaves room for side-by-side mounting without derating, as the side-by-side mounting flag is set. The IP20 finger-safe terminal shroud on the front and at the terminals means it can sit on a live panel rail without additional guarding, though pollution degree 3 (conductive or dry non-conductive pollution) is the rated environment. The headline 10 A at AC-12 is the resistive-load rating — the current the contactor can make and break with a power factor near unity. For motor loads, the AC-3 rating (not explicitly listed in this extract) typically governs, but the AC-2 rating at 400 V is 3 kW, and AC-4 at 400 V is 6.5 A, which tells you the contactor handles reversing or inching duty cycles where the motor is switched under load. The coil hold-in is lower, but the pick-up surge is what you size the control circuit for. Short-circuit coordination is specified: with type 2 coordination (minimal damage to the contactor after a fault), a gL/gG fuse rated 20 A is required; type 1 coordination (contactor may need replacement after fault) allows a 35 A fuse. This matters for panel selectivity studies — if the upstream protection is a 20 A fuse, the contactor is protected to type 2; if a 35 A fuse, expect to replace the contactor after a bolted fault.","metaTitle":"Siemens 3RT1015-2AP02 SIRIUS Power Contactor, S00 Size, 24 V","metaDescription":"Siemens 3RT1015-2AP02 SIRIUS power contactor, size S00, 24 VDC coil, spring-loaded terminals, 10 A rated operational current. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=204602&mlfb=3RT1015-2AP02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AP02/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"The contactor is rated 10 A at AC-12 (resistive), with a 24 VDC coil. Motor ratings include 3 kW at AC-2, 400 V and 6.5 A at AC-4, 400 V. The coil draws 10 A at 24 V rated value. Short-circuit protection requires a gL/gG fuse: 20 A for type 2 coordination, 35 A for type 1."},{"question":"What is the physical size and mounting?","answer":"It is a size S00 contactor, 45 mm wide, 60 mm tall, 73 mm deep. It mounts via screw or snap-on onto a 35 mm DIN rail per EN 50022. Side-by-side mounting is permitted without derating."},{"question":"What wire sizes does the spring-loaded terminal accept?","answer":"The spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-2AP02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-2AP02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}