{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-2AP02-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-2AP02-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-2AP02-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AP02-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1015-2AP02-ZW98 power contactor, size S00, 3 kW at AC-2 400 V, spring-loaded terminals, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"Termination is via spring-loaded terminals for the main current circuit, accepting 2x (0.25... 2.5 mm²) solid or stranded wire. Front face carries IP20 protection. Clearance to grounded metal at the side is 6 mm. For Type 1 coordination (the contactor may need replacement after fault), a 35 A gL/gG fuse is allowed. The AC-2 rating of 3 kW at 400 V is the motor-switching figure that matters for slip-ring motor applications. AC-4 at 400 V is rated at 6.5 A — for plugging or inching duty. The AC-12 maximum operating current is 10 A, covering resistive loads. Auxiliary contact ratings span 24 V (10 A) down to 220 V (0.3 A) and 230 V (6 A), covering a wide range of control voltages. Mechanical endurance is typical at 30 million operating cycles — a figure that reflects the contactor's design life under normal switching conditions, not the electrical endurance under load.","metaTitle":"Siemens 3RT1015-2AP02-ZW98 SIRIUS Power Contactor, S00, 3 kW","metaDescription":"Siemens SIRIUS 3RT1015-2AP02-ZW98 power contactor, size S00, 3 kW at AC-2 400 V. Spring-loaded terminals, screw/snap-on DIN rail mount. Active production. Source to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"3.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"18 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=370335&mlfb=3RT1015-2AP02-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2AP02-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative — the 3RT1016-2AP02?","answer":"The 3RT1016-2AP02 is a larger frame size (S0 vs S00) and carries higher current ratings. It will not drop into a panel wired for the S00 without rewiring the power circuit and checking the DIN-rail footprint. Use the 3RT1016 only if you need the higher rating and can accommodate the larger physical size."},{"question":"What wire sizes does the spring-loaded terminal accept?","answer":"Main current circuit terminals accept 2x (0.25... 2.5 mm²) solid or stranded conductors, or 2x (24... 14) AWG."},{"question":"What compliance documentation is available for this part?","answer":"As a standard Siemens SIRIUS catalogue item, the 3RT1015-2AP02-ZW98 typically carries CE, UL, CSA, and CCC approvals, with RoHS and REACH compliance declarations available from the manufacturer. Specific certification markings should be confirmed on the nameplate or via the product documentation bundle."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-2AP02-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-2AP02-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}