{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1015-2BB41-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1015-2BB41-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RT1015-2BB41-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2BB41-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1015-2BB41-ZW98, 24 VDC coil, 10 A rated operational current, spring-loaded terminals, screw and snap-on mounting for 35 mm DIN rail.","salesMarkdown":"The magnet coil is rated for 24 V DC, drawing 3.3 W on closing and 3.3 W holding, so the control transformer or DC supply needs to deliver that continuously. The contactor is rated for AC-3 duty at 400 V at 3 kW, and AC-4 at 400 V at 6.5 A — the AC-3 figure is the one that governs motor switching in most conveyor, pump, and fan applications. Rated operational current at 24 V is 10 A (AC-12), which covers resistive and lightly inductive loads. For motor duty at 400 V, the AC-3 rating is 3 kW — that's the number to match against your motor nameplate. Main circuit connections use spring-loaded terminals accepting 2x (0.25... 2.5 mm²) solid or stranded, or 2x (24... 14 AWG). No screw torque to verify — just strip to 8 mm and push in. The auxiliary contact block is rated for 10 A at 24 V, 6 A at 230 V, and 0.3 A at 220 V DC, so check your control voltage before wiring the aux. That determines the fuse size in your feeder circuit — type 2 means the contactor remains usable after a fault, type 1 means it may need replacement. Dimensions: 45 mm wide, 60 mm high, 73 mm deep — fits the standard S00 footprint. Side-by-side mounting is permitted with 6 mm spacing to adjacent devices.","metaTitle":"Siemens 3RT1015-2BB41-ZW98 SIRIUS Power Contactor, 24 VDC Co","metaDescription":"Siemens SIRIUS 3RT1015-2BB41-ZW98 power contactor, size S00, 24 VDC coil, 10 A rated operational current, spring-loaded terminals, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"3.5 kW","at 690 V rated value":"4 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"3 kW","at AC-4 at 400 V rated value":"6.5 A","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"18 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=321774&mlfb=3RT1015-2BB41-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1015-2BB41-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"The coil is 24 V DC drawing 3.3 W. Main contacts are rated 10 A at 24 V (AC-12), 3 kW at 400 V (AC-3), and 6.5 A at 400 V (AC-4). Connections are spring-loaded terminals accepting 2x (0.25...2.5 mm²) solid or stranded."},{"question":"What are the physical dimensions and mounting?","answer":"Width 45 mm, height 60 mm, depth 73 mm. Mounts on 35 mm DIN rail per DIN EN 50022 via screw or snap-on. Side-by-side mounting requires 6 mm spacing."},{"question":"What short-circuit protection is required?","answer":"For type 2 coordination, use a gL/gG 20 A fuse upstream. For type 1 coordination, use gL/gG 35 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1015-2BB41-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1015-2BB41-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}