{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1AM25-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1AM25-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1AM25-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AM25-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S00, 3RT1016-1AM25-ZX95, 24 VDC coil, 10 A rated, screw terminals, 45 mm width, IP20 front.","salesMarkdown":"## What this SIRIUS S00 contactor is and where it lands The screw-type terminals accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, with a max of 2x (0.75 to 4 mm²) — that's the wiring envelope for the main current circuit. Side-by-side mounting is allowed — no derating gap required between units on the rail. For Type 1 coordination (contactor may need replacement but the installation is safe), the fuse goes up to 35 A gL/gG. That's the difference between a fuse that protects the contactor itself versus one that only clears the fault. ## Switching capacity across voltages — where this contactor works hardest At 24 V rated value the contactor handles 10 A; at 230 V it's rated 6 A; at 400 V it drops to 3 A. For motor loads in AC-2 duty at 400 V, the rated power is 4 kW; in AC-4 duty at 400 V, the operating current is 8.5 A. The 690 V rating pushes 5.5 kW. That spread tells you this is a general-purpose S00 contactor — fine for small motors, resistive heaters, and lighting banks up to about 5.5 kW at higher line voltages. The 30 million mechanical cycles typical life means it outlasts most panel refreshes. ## Environmental limits and installation conditions","metaTitle":"Siemens 3RT1016-1AM25-ZX95 SIRIUS Power Contactor, S00, 24 V","metaDescription":"Siemens SIRIUS 3RT1016-1AM25-ZX95 power contactor, size S00, 24 VDC coil rated 10 A. Screw terminals, 45 mm wide, current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"208 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"208 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"3","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=481993&mlfb=3RT1016-1AM25-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AM25-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1016-1AM25-ZX95?","answer":"The listed depth is 114 mm, with a width of 45 mm and height of 57.5 mm."},{"question":"What wire sizes does the screw terminal accept?","answer":"The main current circuit screw terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, with a maximum of 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16) and 2x (18 to 14), with a single 12 AWG."},{"question":"Where can I buy 3RT1016-1AM25-ZX95?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"Will 3RT1016-1AM25-ZX95 drop into a panel designed for 3RT1016-1AG61?","answer":"Both are S00 frame size contactors on the same 45 mm DIN footprint, so the mechanical fit is identical. The difference is the coil voltage and switching ratings — verify the coil matches your control voltage before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1AM25-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1AM25-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}