{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1AP01-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1AP01-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1AP01-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AP01-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1016-1AP01-1AA0, 10 A rated operational current at 24 V, screw terminals, 45 mm width.","salesMarkdown":"Rated operational current at 24 V is 10 A (AC-12), and at 230 V it carries 6 A. For motor duty, the AC-2 rating at 400 V is 4 kW, and the AC-4 rating at 400 V is 8.5 A. The control supply coil accepts 0.8 to 1.1 times the rated voltage at both 50 Hz and 60 Hz, with a rated value of 230 V at 50 Hz and 230 V at 60 Hz. Pollution degree 3 rating suits industrial environments. The terminal accepts solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and a maximum of 2x (0.75 to 4 mm²). For AWG, it accepts 2x (20 to 16), 2x (18 to 14), and 1x 12. This allows dense packing on the DIN rail while maintaining thermal separation. The contactor has one instantaneous contact. For type of coordination 1, the required fuse is gL/gG 35 A. For type of coordination 2, the required fuse is gL/gG 20 A. This distinction matters for selectivity studies: coordination 1 allows the contactor to be damaged after a short circuit (but no fire risk), while coordination 2 keeps the contactor operational after clearing the fault. The mechanical endurance is typical 30 million operations, which reflects the S00 frame's suitability for high-cycle applications.","metaTitle":"Siemens 3RT1016-1AP01-1AA0 SIRIUS Power Contactor, S00, 10A","metaDescription":"Siemens SIRIUS 3RT1016-1AP01-1AA0 power contactor, size S00, 10 A rated operational current at 24 V. Screw terminals, 45 mm width, IP20. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=380444&mlfb=3RT1016-1AP01-1AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AP01-1AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT1016-1AP01-1AA0?","answer":"The 3RT1016-2AP02 is a peer in the same S00 frame size. The key difference is that the 2AP02 variant uses spring-cage terminals instead of screw-type terminals. If your panel is wired for screw terminals, the 1AP01-1AA0 is the direct fit without rewiring. The 3RT1017-1AP01 is the next size up (S0 frame) with higher current ratings."},{"question":"What are the physical dimensions of this contactor?","answer":"Width is 45 mm, height is 57.5 mm, and depth is 72 mm. It mounts on 35 mm DIN rail per EN 50022."},{"question":"What wire sizes does the screw terminal accept?","answer":"Solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). AWG: 2x (20 to 16), 2x (18 to 14), 1x 12."},{"question":"Will 3RT1016-1AP01-1AA0 drop into a panel specified for 3RT1016-2AP02?","answer":"The physical footprint is identical — same S00 frame, same 45 mm width, same DIN rail mounting. The difference is the terminal type: screw terminals on this part versus spring-cage on the 2AP02. If the panel wiring is already terminated with ferrules or bare wire for spring-cage, you would need to change the termination method for screw terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1AP01-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1AP01-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}