{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1AP05-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1AP05-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1AP05-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AP05-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S00, 3RT1016-1AP05-ZX95, 4.5 kW at 500 V, 5.5 kW at 690 V, screw-type terminals, 35 mm DIN rail.","salesMarkdown":"For motor duty, the contactor is rated 4.5 kW at 500 V and 5.5 kW at 690 V. Auxiliary contact block provides 3 instantaneous contacts, rated 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V, among other voltage taps. This covers feedback to a PLC or holding-circuit interlocking without an add-on block. Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. This covers typical motor feeder cables up to 4 mm² without needing lug adapters. The contactor occupies 45 mm width, 57.5 mm height, and 114 mm depth. Side-by-side mounting is permitted with zero side clearance, so multiple units pack tightly on the DIN rail. For short-circuit coordination, Type 1 coordination requires a 35 A gL/gG fuse; Type 2 coordination requires a 20 A gL/gG fuse. This determines the upstream protective device selection for the panel schedule. Mechanical service life is typical 30,000,000 operations, which reflects the contactor's endurance in high-cycle applications like conveyor or packaging machinery. The operating voltage range factor is 0.8 to 1.1 at 50 Hz and 0.85 to 1.1 at 60 Hz, meaning the coil holds in across a sag down to 80% of nominal at 50 Hz, and 85% at 60 Hz.","metaTitle":"Siemens 3RT1016-1AP05-ZX95 SIRIUS Contactor, Size S00, 4.5 k","metaDescription":"Siemens 3RT1016-1AP05-ZX95 SIRIUS power contactor, size S00. Rated 4.5 kW at 500 V, 5.5 kW at 690 V. Screw terminals, 35 mm DIN rail mount. Current lifecycle stage. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"3","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=428379&mlfb=3RT1016-1AP05-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AP05-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT1016-1AP05-ZX95?","answer":"The peer 3RT1016-2AP02 is a similar S00 frame contactor but uses spring-cage terminals instead of screw-type. If your panel wiring is already terminated for screw clamps, the -ZX95 variant avoids re-termination. For new builds where spring-cage is preferred, the -2AP02 offers faster wiring."},{"question":"Will 3RT1016-1AP05-ZX95 drop into a panel specified around 3RT1016-2AP02 without rewiring?","answer":"The physical footprint (45 mm width, 57.5 mm height, 114 mm depth) and DIN rail mounting are identical between the two. The difference is terminal type: the -ZX95 uses screw terminals, while the -2AP02 uses spring-cage. If the panel was wired for spring-cage, you would need to re-terminate or use ferrule adapters."},{"question":"What are the key motor power ratings for this contactor?","answer":"It is rated 4.5 kW at 500 V and 5.5 kW at 690 V. For AC-4 duty at 400 V, the rated operational current is 8.5 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1AP05-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1AP05-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}