{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1AR62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1AR62","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1AR62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AR62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT1016-1AR62, 24 VDC coil, screw-type terminals, 45 mm width, 57.5 mm height, 72 mm depth, rated AC-2 4 kW / AC-4 8.5 A at 400 V.","salesMarkdown":"It mounts via screw and snap-on onto 35 mm DIN rail per EN 50022, and the screw-type terminals accept solid conductors from 2x (0.5 to 1.5 mm²) up to 2x (0.75 to 4 mm²). The coil pulls in at 24 VDC; the contactor is rated for AC-2 duty at 4 kW and AC-4 duty at 8.5 A, both at 400 V. ## Duty ratings and coordination For AC-2 (slip-ring motor switching) the contactor handles 4 kW at 400 V; for AC-4 (plugging/inching) it's rated 8.5 A at 400 V. The DC switching capacity at 24 V is 10 A, dropping to 0.3 A at 220 V. With type of coordination 2, the required fuse is gL/gG 20 A; with type 1 coordination, gL/gG 35 A. Mechanical life is typical 30 million operations. ## Panel integration Side-by-side mounting is permitted with 6 mm spacing at the side. Front and terminal protection is IP20. The Size S00 footprint (45 mm wide × 57.5 mm high × 72 mm deep) fits standard control-panel layouts.","metaTitle":"Siemens 3RT1016-1AR62 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens 3RT1016-1AR62 SIRIUS power contactor, Size S00, 24 VDC coil. AC-2 4 kW / AC-4 8.5 A at 400 V. Screw terminals, DIN rail mount. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"400 ... 440 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=421223&mlfb=3RT1016-1AR62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AR62/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1016-1AR62?","answer":"The depth is 72 mm."},{"question":"What solid wire sizes does 3RT1016-1AR62 accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max. 2x (0.75 to 4 mm²) solid conductors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1AR62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1AR62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}