{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1AV01-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1AV01-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1AV01-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AV01-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1016-1AV01-ZX95 power contactor, Size S00, 45 mm width, 72 mm depth, screw-type terminals, IP20 finger-safe front, DIN rail mount.","salesMarkdown":"Rated for AC-4 duty at 8.5 A and 4 kW at 400 V, and 5.5 kW at 690 V, this contactor handles reversing or inching applications where the motor is switched under load. For straight starting (AC-3), the contactor is rated 4.5 kW at 500 V and 5.5 kW at 690 V — per the datasheet, these are the motor power limits for normal across-the-line starts. Type 1 coordination requires a 35 A gL/gG fuse; Type 2 coordination requires a 20 A gL/gG fuse. The difference governs whether the contactor survives a short-circuit fault without welding — Type 2 keeps it reusable, Type 1 may require replacement. Select the fuse per your panel's selectivity study. Main circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. Strip length and torque values per the terminal marking — the screw clamp needs a proper screwdriver, not a Pozidriv. One normally open auxiliary contact is built in (instantaneous contact). For additional auxiliaries, the Size S00 frame accepts side-mounting blocks — the 6 mm side clearance per the spec allows stacking without derating. The 3RT1016-1AV01-ZX95 carries the -ZX95 suffix, which typically indicates a special version or customer-specific variant. Verify that the -ZX95 marking matches your panel's approved parts list before committing the line — a standard 3RT1016-2AP02 may be a drop-in alternative if the special marking is not required.","metaTitle":"Siemens 3RT1016-1AV01-ZX95 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens 3RT1016-1AV01-ZX95 SIRIUS power contactor, Size S00, 45 mm width, 72 mm depth. AC-4 8.5 A at 400 V, 5.5 kW at 690 V. Current lifecycle stage. Screw terminals, IP20 front. D","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"400 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=530484&mlfb=3RT1016-1AV01-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AV01-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"AC-4 rated current is 8.5 A at 400 V. Motor power ratings are 4.5 kW at 500 V and 5.5 kW at 690 V. Mechanical life is 30 million cycles typical. Operating temperature range is -25 to +60 °C."},{"question":"What wire sizes does the screw terminal accept?","answer":"The main circuit terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."},{"question":"What fusing is required for Type 1 and Type 2 coordination?","answer":"Type 1 coordination requires a 35 A gL/gG fuse. Type 2 coordination requires a 20 A gL/gG fuse. Select based on whether you need the contactor to remain functional after a short-circuit fault."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1AV01-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1AV01-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}